Connecting
6.5 Division options
Example 5: Controlling a SITOR thyristor set 6QG12
The information on cables, cable lengths, and module division provided in Example 3 also
largely applies to this example.
The firing pulse transformer module is completely divided up. The small individual boards
containing the firing pulse transformers can be connected to the power unit instead of the
old-style small firing pulse transformer boards. The fuse monitoring and voltage
measurement equipment is mounted in the immediate vicinity of the SITOR set.
Connecting current transformers
Rear view
92
①
Current transformers
②
Remove the connection between
the current transformers and
module A7 and connect the current
transformer cables directly to the
current transformers' screw
terminals.
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A