Siemens SINAMICS DCM Operating Instructions Manual page 149

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Terminal,
Function
connection
XIMP24 control for firing pulse transformers for the thyristors
IMP24
For thyristor V24
P24
X24
G, K
Firing cable, thyristor V24
XIMP25 control for firing pulse transformers for the thyristors
IMP25
For thyristor V25
P24
X25
G, K
Firing cable, thyristor V25
XIMP26 control for firing pulse transformers for the thyristors
IMP26
For thyristor V26
P24
X26
G, K
Firing cable, thyristor V26
Outputs for voltage measurement
X12_1
Armature line voltage W
X14_1
Armature line voltage U
X15_1
Armature voltage 1C1
X16_1
Armature line voltage V
X25_1
Armature voltage 1D1
"Firing pulse transformer module"
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
6.16 Connector assignment (terminals, Faston mounting tabs, ribbon cables)
Technical data, comments
Only to be connected if the firing pulse transformer module is divided
up (see terminal strip XIMP_4)
Firing pulse (see below) gate (G) to auxiliary cathode (K)
Only to be connected if the firing pulse transformer module is divided
up (see terminal strip XIMP_4)
Firing pulse (see below) gate (G) to auxiliary cathode (K)
Only to be connected if the firing pulse transformer module is divided
up (see terminal strip XIMP_4)
Firing pulse (see below) gate (G) to auxiliary cathode (K)
When the firing cables are connected to the thyristors in the power
unit, the line and armature voltages are automatically present at the
firing pulse transformer module.
These voltages can then be routed from here (connections X12_1,
etc.) to the voltage measurement equipment, without having to route
any additional cables to the power unit.
See also Chapter "Connecting the external power unit".