Siemens SINAMICS DCM Operating Instructions Manual page 391

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Bit
Meaning
9
Control request
"1" is always present
10
n setpoint reached or exceeded
Note:
The message is parameterized as follows: p50373 (threshold value), p50374 (hysteresis)
See FP8020 and FP2537
11
I or M limit not reached (when
p0922 = 1 or 352)
I or M limit not reached (when
p0922 = 20)
12
Holding brake released
(when p0922 = 1 or 352)
Reserved (when p0922 = 20)
13
No motor overtemperature alarm
14
Motor rotates forward
(n_act ≥ 0)
15
Reserved
(when p0922 = 1 or 352)
CDS display
(when p0922 = 20)
ZSW2 (status word 2)
See function diagram [2454].
Table 10- 14 Status word 2 (ZSW2)
Bit
Meaning
0
1 = Drive data set selection DDS effective, bit 0
1
1 = Drive data set selection DDS effective, bit 1
2
Reserved
3
Reserved
4
Reserved
5
1 = Alarm class bit 0
6
1 = Alarm class bit 1
7
Reserved
8
Reserved
9
Reserved
10
1 = Enable pulses
11 to 15
Reserved
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
Explanation
1
The automation system is requested to assume control.
0
Control is only possible at the unit itself
1
n setpoint reached or exceeded
0
n setpoint not reached
1
I or M limit not reached
0
I or M limit reached or exceeded
1
I or M limit not reached
0
I or M limit reached or exceeded
1
Holding brake is released
0
Holding brake is closed
1
Alarm overtemperature motor not pending
0
Motor overtemperature alarm pending
1
Motor rotates forward (n_act ≥ 0)
0
Motor does not rotate forward (n_act < 0)
1
CDS selection bit 0 selected
0
CDS selection bit 0 not selected
Descriptions of functions
10.3 Communication according to PROFIdrive
Interconnection parameter
p2081[0] = r0051.0
p2081[1] = r0051.1
-
-
-
p2081[5] = r2139.11
p2081[6] = r2139.12
-
-
-
p2081[10] = r0899.11
-
Parameter
BO: r0899.9
BO: r2199.1
BO: r1407.7
(inverted)
BO: r0056.13
(inverted)
BO: r0899.12
BO: r2135.14
(inverted)
BO: r2197.3
BO: r0836.0
389