Siemens SINAMICS DCM Operating Instructions Manual page 477

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Activating the diagnostics function
The diagnostics function is activated or deactivated via the parameterization of the relevant
configuration tool (HW Config, TIA Portal, etc.).
Figure 10-41 Activation of PROFINET
The following parameter assignments are possible:
Setting
Inactive
PROFIdrive error classes
When establishing the communication between SINAMICS and a master/controller, the
activated diagnostics mode of this master/controller is first transferred to the drive. With
activated diagnostics, SINAMICS first transfers all pending messages to the
master/controller.
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
10.5 Communication via PROFINET IO
Code for parameter assignment
0
1
Descriptions of functions
475

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics dc master

Table of Contents