Commissioning
8.7 Commissioning optional additional modules
You can also subsequently activate option module CBE20.
● Start the configuration wizard via "Control Unit" -> Configuration" -> "Wizard..."
● In the "Option module" screen form, select CBE20
● Work through the remainder of the wizard up to the end
● Go online
● Load the project to the drive
8.7.3.3
Deleting from the drive online
Removing a CBE20 without STARTER always leads to the loss of the parameter
assignments which are replaced by the factory settings.
p0009 = 30
p0976 = 1
(recent commissioning)
8.7.3.4

Deleting offline with STARTER

CBE20 can only be removed in the offline state.
● Start the configuration wizard via "Control Unit" -> Configuration" -> "Wizard..."
● In the "Option module" screen form, deselect CBE20
● Work through the remainder of the wizard up to the end
● Remove the CBE20 option board from the Control Unit
● Go online
● Load the project to the drive