6.16.10
Assignment of the RS485 cable to the AOP30
Note
A 24 V power supply is required to operate the AOP30. For a maximum cable length of
50 m, this can be taken from the CUD of the SINAMICS DCM. An external power supply
must be used for cable lengths > 50 m.
RS485 cable with 24 V DC power supply from the CUD – max. 50 m
RS485 cable when operating with 2 CUDs, 24 V DC power supply from one CUD – max. 50 m
RS485 cable when supplying the AOP30 from an external 24 V DC source – max. 200 m
X524
Plug terminals
X540
9-pin Sub-D socket
Figure 6-47
Assignment, RS485 cable
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
6.16 Connector assignment (terminals, Faston mounting tabs, ribbon cables)
X178
Plug terminals
Connecting
155