Siemens SINAMICS DCM Operating Instructions Manual page 130

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Connecting
6.16 Connector assignment (terminals, Faston mounting tabs, ribbon cables)
6.16.2
Field circuit
Table 6- 15
Type of terminals for connecting the field circuit
Type
Connection capacity
Stripped length
Tightening torque
Table 6- 16
Assignment of the connections for the field circuit
Terminal
Function
3U1, 3W1
Line supply connection
3C, 3D
Field winding connection
6.16.3
Electronic power supply
Table 6- 17
Terminal type, electronics power supply
Type
Connection capacity
Stripped length
Table 6- 18
Assignment of terminals for the electronics power supply
Terminal
Function
XP24V
+
24 V infeed
-
"Power interface for the Control Module" module
128
20E/4DS terminal strip
Rigid/flexible (mm
/mm
): 6-16 / 6-10
2
2
8 mm
1.5 Nm
Technical data
2 AC 400 V (-20%), 2 AC 480 V (+10%)
325/373 rated V DC voltage
with 2-ph. 400/480 V AC line connection
Wago 256 spring-loaded terminal
0.08 ... 2.5 mm
, AWG 18-12
2
5-6 mm
Technical data
18 V to 30 V DC; current consumption 1 A ... 5 A
Recommended conductor cross-section 1.5 mm
Internal protection with F200 fuses (6.3 A, time-lag. See Chapter
"Fuses (Page 116)"),
external protection 6 A ... 16 A, B or C characteristic
2