p19 Instrument correction factor 5 (number of
segmental points ≥ 5)
p20 Sensor correction factor 5 (number of
segmental points ≥ 5)
p21 Uncorrected value 6 (number of
segmental points ≥ 6)
p22 Instrument correction factor 6 (number of
segmental points ≥ 6)
p23 Sensor correction factor 6 (number of
segmental points ≥ 6)
p24 Uncorrected value 7 (number of
segmental points ≥ 7)
p25 Instrument correction factor 7 (number of
segmental points ≥ 7)
p26 Sensor correction factor 7 (number of
segmental points ≥ 7)
p27 Uncorrected value 8 (number of
segmental points ≥ 8)
p28 Instrument correction factor 8 (number of
segmental points ≥ 8)
p29 Sensor correction factor 8 (number of
segmental points ≥ 8)
p30 Uncorrected value 9 (number of
segmental points ≥ 9)
p31 Instrument correction factor 9 (number of
segmental points ≥ 9)
p32 Sensor correction factor 9 (number of
segmental points ≥ 9)
p33 Uncorrected value 10 (number of
segmental points ≥ 10)
p34 Instrument correction factor 10 (number
of segmental points ≥ 10)
p35 Sensor correction factor 10 (number of
segmental points ≥ 10)
p36 Uncorrected value 11 (number of
segmental points ≥ 11)
p37 Instrument correction factor 11 (number
of segmental points ≥ 11)
p38 Sensor correction factor 11 (number of
segmental points ≥ 11)
p39 Uncorrected value 12 (number of
segmental points ≥ 12)
p40 Instrument correction factor 12 (number
of segmental points ≥ 12)
p41 Sensor correction factor 12 (number of
segmental points ≥ 12)
Query
SCtrlCalibAI[,p1,p2,p3]?
Example Set three correction points on channel 0001
(measurement range: 0 to 1.0000 V). Set the
correction points as follows: when the input
value is 0 V, the output value is 0.0010 V;
when the input value is 0.5000 V, the output
value is 0.5020 V; when the input value is
1.0000 V, the output value is 0.9970 V.
SCtrlCalibAI,0001,Appro,
3,0,10,5000,5020,10000,9970
Description
This command is valid when a PID Control Module is
installed.
If p4=Off, you cannot set p5 and subsequent
parameters.
You cannot set correction points beyond the number
of points specified by p5.
IM 04L51B01-17EN
If the AI channel input type (p4 of the
command) is set to Skip or DI, you cannot specify
anything other than p4=Off.
SCtrlRangeAO
Transmission Output
Sets the transmission output range of the AO terminal of a
PID control module.
Syntax
SCtrlRangeAO,p1,p2,p3,p4,p5,p6,p7
p1 Unit number
p2 Module number
p3 AO terminal number (AO1, AO2)
p4 Transmission output (On, Off)
Off
On
p5 Terminal number
OUT1
PV1
SP1
OUT2
PV2
SP2
p6 Scaling low limit (–30000 to 30000)
p7 Scaling high limit (–30000 to 30000)
Query
SCtrlRangeAO[,p1,p2,p3]?
Example Set the output of AO1 of module number 2
connected to the main unit to PV1.
SCtrlRangeAO,0,2,AO1,On,
PV1,-30000,30000
Description
This command is valid when a PID Control Module is
installed.
If p4=Off, p5 will be set in the following combinations.
Control mode
Single loop or Cascade
PV switching
p5 cannot be set to OUT2, PV2 or SP2 when the
control mode is "PV switching".
2.4 Setting Commands
SCtrlRangeAI
p3=AO1
p3=AO2
p5=OUT1
p5=OUT2
p5=OUT1
p5=OUT1
2-81
1
2
App