FSnap
Snapshot [GX/GP]
Outputs a snapshot data (screen image data) file.
Syntax
FSnap,p1
p1 Screen image data output (GET)
Example Acquire screen image data.
FSnap,GET
Description
A PNG image file will be stored in the data block of the
page
binary output file (see
FUser
Outputs the User Level
Outputs information about the users who are currently
logged in.
Syntax
FUser,p1
p1 Information about the users who are
currently logged in
0
Refer to your own user information.
1
Refer to information about all users
who are currently logged in.
Refer to information 2 of the user who
2
is currently logged in
Refer to information 2 of all users who
3
are currently logged in
Example Refer to information about all users who are
currently logged in.
FUser,1
Description
For the ASCII output format, see
FAddr
Outputs the IP Address
Outputs the recorder IP address information.
Syntax
FAddr,p1
p1 Address output (IP)
Output address information that includes
the IP address, subnet mask, default
gateway, and DNS server as well as the
host name and domain name.
Example Output the recorder IP address information.
FAddr,IP
Description
For the ASCII output format, see
IM 04L51B01-17EN
2-119).
page
2-126.
page
2-130.
FStat
Outputs the Recorder Status
Outputs the recorder status.
Syntax
FStat,p1
p1 Status output (0)
0
Status 1 to 4 output
1
Status 1 to 8 output
Example Output the recorder status.
FStat,0
Description
For the ASCII output format, see
FLog
Outputs the Log
Outputs the alarm summary, message summary, error log,
etc.
Syntax
FLog,p1,p2,p3
p1 Status output (0)
ALARM
Alarm summary
MSG
Message summary
Event log
EVENT
ERROR
Error log
DHCP
Ethernet address setting log
GENERAL General communication log
MODBUS Modbus log
FTP
FTP client log
SNTP
SNTP client log
E-mail log
MAIL
WEB
Web log
SLMP
SLMP log
CALARM Control alarm summary log
CTRL
Control summary log
p2 Maximum log readout length
p1
ALARM
MSG
GENERAL
MODBUS
CALARM
CTRL
Other than those
above.
p3 Batch group number
All
All batch group numbers
1 to the
Batch group number
number
used
Example Output 600 alarm summary entries.
FLog,ALARM,600
Description
For the ASCII output format, see
p3 is valid when multi batch is in use and p1={alarm,
msg, event}. Omitting it is equivalent to specifying all
batch groups.
2.5 Output Commands
page
2-131.
Read range
1 to 1000
1 to 500
1 to 200
1 to 50 (1 to 200 for the
GX20-2/GP20-2)
1 to 500
1 to 1000
1 to 50
page
2-134.
2-95