YOKOGAWA GX10 User Manual page 36

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

2.4 Setting Commands
SEventData
Event Data Recording
Sets the event data recording mode.
Syntax
SEventData,p1,p2,p3,p4,p5,p6
p1 Scan group (1 or 2)
p2 Recording interval
p3 Operation mode
Free
SingleTrigger After a trigger event
RepeatTrigger After a trigger event
p4 Data length
30min, 1h, 2h, 3h, 4h, 6h, 8h, 12h, 1day,
2day, 3day, 5day, 7day, 14day, 31day)
p5 Pre-trigger (0, 5, 25, 50, 75, 95, 100) [%]
p6 Trigger source key (Off, On)
Query
SEventData[,p1]?
Example Record event data in Free mode at a recording
interval of 1 second. Separate the data into
different files every 2 hours.
SEventData,1,1s,Free,2h
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
You cannot choose a recording interval that is shorter
than the scan interval.
You cannot choose a recording interval that is not an
integer multiple of the scan interval.
p1 = 2 is valid when the measurement mode is set to dual
interval.
The recording interval (p2) can be set in the following
range.
Measurement mode
Normal
High speed
(Note 1)
Dual interval
(Note 1)
1
There are limits to the recording intervals less than or
equal to 50 ms depending the scan interval.
The recording intervals (p2) less than or equal to 50
ms can be set in the following range.
2-18
(see "Description.")
Starts recording at
recording start and
stops recording at
recording stop.
occurs, the recorder
will record for the
specified time and
stop.
occurs, the recorder
will record for the
specified time and
stop. Then, the
recorder will enter the
trigger-wait state.
(2min, 5min,
10min, 20min,
Options (p2)
100ms, 200ms, 500ms, 1s, 2s, 5s,
10s, 15s, 20s, 30s, 1min, 2min,
5min, 10min, 15min, 20min, 30min
1ms,2ms,5ms,10ms,20ms,50ms,
100ms, 200ms, 500ms, 1s, 2s, 5s,
10s, 15s, 20s, 30s, 1min, 2min,
5min, 10min, 15min, 20min, 30min
1ms,2ms,5ms,10ms,20ms,50ms,
100ms, 200ms, 500ms, 1s, 2s, 5s,
10s, 15s, 20s, 30s, 1min, 2min,
5min, 10min, 15min, 20min, 30min
Scan interval
1ms
2ms
5ms
10ms
20ms
50ms
There are limits to the recording interval (p2)
depending on the model, scan interval, and number of
recording channels (see SRecEvent).
Data length (p4) can be set to 2min or 5min when the
measurement mode is set to high speed.
Data length (p4) can be set to 5min when the
measurement mode is set to dual interval.
This setting is valid when event data recording is
enabled (recording mode of the
When the advanced security function (/AS) is enabled,
p3 is fixed to Free.
When the multi batch function (/BT) is enabled, p3 is
fixed to Free.
Recording intervals less than or
equal to 50 ms
1ms, 2ms, 5ms, 10ms, 20ms,
50ms
2ms, 10ms, 20ms, 50ms
5ms, 10ms, 20ms, 50ms
10ms, 20ms, 50ms
20ms
50ms
SMemory
command).
IM 04L51B01-17EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gm10Gx20Gp20Gp10

Table of Contents