SCtrlOvershoot
Control Detail Setting 5 (Control Output
Suppressing Function)
Sets the control output suppressing function (overshoot-
suppressing function)
Syntax
SCtrlOvershoot,p1,p2
p1 Loop number
p2 Control output suppressing function
Off
Normal
Query
SCtrlOvershoot[,p1]?
Example For loop number L022, set overshoot to normal
mode.
SCtrlOvershoot,L022,Normal
Description
•
This command is valid when a PID Control Module is
installed.
SCtrlGroupSW
Control Group Use/Not
Sets whether to use control groups
Syntax
SCtrlGroupSW,p1,p2
p1 Display group number
p2 Use/Not
Off
On
Query
SCtrlGroupSW[,p1]?
Example Set the group of display group number 8 to not
use.
SCtrlGroupSW,8,Off
Description
•
This command is valid when a PID Control Module is
installed.
•
The selectable range of display group numbers (p1)
varies depending on the model.
SCtrlGroupName
Control Group Name
Sets the control group name
Syntax
SCtrlGroupName,p1,p2
p1 Display group number (1 to 10)
GX10/GX20-1/GM10-1: 1 to 5
GX20-2/GM10-2: 1 to 10
p2 Group name (up to 16 characters, UTF-8)
Query
SCtrlGroupName[,p1]?
Example Set the group name of display group number 8
to "Group8."
SCtrlGroupName,8,'Group8'
Description
•
This command is valid when a PID Control Module is
installed.
•
The selectable range of display group numbers (p1)
varies depending on the model.
IM 04L51B01-17EN
Not Use
Normal mode
Not Use
Use
SCtrlGroupSplit
Control Group Divisions [GX/GP]
Sets the number of control group divisions
Syntax
SCtrlGroupSplit,p1,p2
p1 Display group number (1 to 10)
GX10/GX20-1/GM10-1: 1 to 5
GX20-2/GM10-2: 1 to 10
p2 Number of divisions (2, 4, 6, 8)
The number of divisions cannot be set to 8
on the GX10.
Query
SCtrlGroupSplit[,p1]?
Example Set the number of divisions of display group
number 8 to 4.
SCtrlGroupSplit,8,4
Description
•
This command is valid when a PID Control Module is
installed.
•
The selectable range of display group numbers (p1)
varies depending on the model.
SCtrlGroup
Control Group Assignment
Sets loops to assign to control groups
Syntax
SCtrlGroup,p1,p2,p3,p4
p1 Display group number
p2 Setting Number
GX20/GM10: 1 to 8
GX10: 1 to 6
p3 Setting On, Off
Off
On
p4 Type
INT
p5 Loop number
Query
SCtrlGroup[,p1,p2]?
Example Assign L001, L002, L011, L012, L021, and
L022 to the group with display group number 8.
SCtrlGroup,8,1,On,INT,001;SCtrlGro
up,8,2,On,INT,002;SCtrlGroup,8,3,O
n,INT,011;SCtrlGroup,8,4,On,INT,01
2;SCtrlGroup,8,5,On,INT,021;SCtrlG
roup,8,6,On,INT,022;
Description
•
This command is valid when a PID Control Module is
installed.
•
On the GX/GP, p3 cannot be set to On exceeding
the number of divisions. (See the SCtrlGroupSplit
command.)
2.4 Setting Commands
Not set
Set
Loop
2-89
1
2
App