2.4 Setting Commands
DI5
DI5 status output
DI6
DI6 status output
DI7
DI7 status output
DI8
DI8 status output
AI1_BOUT
AI1 burnout
AI1_ADERR
AI1 AD error
AI2_BOUT
AI2 burnout
AI2_ADERR
AI2 AD error
When the output is "Alarm" and the action is "And/
Or"
Syntax
SCtrlRelay,p1,p2,p3,p4,p5,p6,p7,p8
p1 Unit number
p2 Module number
p3 DO number (DO1 to DO8)
p4 Output type
Alarm
p5 Energize/De-energize (Energize, De_
Energize)
Energize
De_
Energize
p6 Action (And, Or)
And
Or
p7 State
Hold
Nonhold
p8 Relay Action on ACK (Normal, Reset)
When the output is "Alarm" and the action is
"Reflash"
Syntax
SCtrlRelay,p1,p2,p3,p4,p5,p6,p7,p8
p1 Unit number
p2 Module number
p3 DO number (DO1 to DO8)
p4 Output type
Alarm
p5 Energize or de-energize
Energize
De_
Energize
p6 Action
Reflash Reflash
p7 Reflash time (500ms, 1s, 2s)
p8 Relay Action on ACK (Normal, Reset)
When the output is "Manual"
Syntax
SCtrlRelay,p1,p2,p3,p4,p5
p1 Unit number
p2 Module number
p3 DO number (DO1 to DO8)
p4 Output type
Manual
p5 Energize or de-energize
Energize
De_
Energize
Query
SCtrlRelay[,p1,p2,p3]?
2-78
COMMON
COMMON
COMMON
COMMON
COMMON
COMMON
COMMON
COMMON
Alarm
Energize
De-energize
Operate when all set alarms are
in the alarm state.
Operate when any of the set
alarms are in the alarm state.
Hold
Nonhold
Alarm
Energize
De-energize
Manual
Energize
De-energize
Example
Set DO1 of module number 2 connected to
the main unit to manual and energize.
SCtrlRelay,0,2,DO1,Manual,Energ
ize
Description
This command is valid when a PID Control Module is
installed.
If p4=CtrlRelay, p6 alarm level is indicated as ALM*_
Lx(*=1 to 8, x=1 or 2). ALM*_OUT_Lx(*=1 to 8, x=1
or 2) indicates the alarm output status including the
relay action.
SCtrlRangeAI
Measurement Input Range
Sets the range of the AI terminal of a PID control module.
Input type is TC or RTD
Syntax
SCtrlRangeAI,p1,p2,p3,p4,p5,p6,p7,
p8,p9
p1 Unit number
p2 Module number
p3 AI terminal number (AI1, AI2)
p4 Input type (TC, RTD)
p5 Range (see "Description.")
p6 Math type (Off)
p7 Span low limit
p8 Span high limit
p9 Bias (–999999 to 999999)
Input type is not TC or RTD and math type is Scaling
Syntax
SCtrlRangeAI,p1,p2,p3,p4,p5,p6,p7,
p8,p9,p10,p11,p12,p13
p1 Unit number
p2 Module number
p3 AI terminal number (AI1, AI2)
p4 Input type (Volt, GS, DI)
p5 Range (see "Description.")
p6 Math type (Scale)
p7 Span low limit
p8 Span high limit
p9 Bias (–999999 to 999999)
p10 Decimal Place (0 to 5)
p11 Scaling low limit
p12 Scaling high limit
p13 Unit (up to 6 characters, UTF-8)
Input type is GS or Volt and math type is square root
Syntax
SCtrlRangeAI,p1,p2,p3,p4,p5,p6,p7,
p8,p9,p10,p11,p12,p13,p14,p15,p16
p1 Unit number
p2 Module number
p3 AI terminal number (AI1, AI2)
p4 Input type (Volt, GS)
p5 Range (see "Description.")
p6 Math type (Sqrt)
p7 Span low limit
p8 Span high limit
IM 04L51B01-17EN