SAlarmMath
Alarm (/MT)
Sets the alarm of a math channel.
Do Not Set Alarms
Syntax
SAlarmMath,p1,p2,p3
p1 Channel number
p2 Alarm number (1 to 4)
p3 Alarm on or off (Off)
Do Not Output Alarms
Syntax
SAlarmMath,p1,p2,p3,p4,p5,p6,p7
p1 Channel number
p2 Alarm number (1 to 4)
p3 Alarm on or off (On)
P4 Alarm type (H, L, TH, TL)
p5 Alarm value (within the span range)
p6 Detection (Off, On)
p7 Output (Off)
Output Alarms
Syntax
SAlarmMath,p1,p2,p3,p4,p5,p6,p7,p8
p1 Channel number
p2 Alarm number (1 to 4)
p3 Alarm on or off (On)
P4 Alarm type (H, L, TH, TL)
p5 Alarm value (within the span range)
p6 Detection (Off, On)
p7 Output
DO
SW
p8 Number
If p7=DO
If p7=SW
Channel Using Logarithmic Math
Syntax
SAlarmMath,p1,p2,p3,p4,p5,p6,p7,p
8,p9
p1 Channel number
p2 Alarm number (1 to 4)
p3 Alarm on or off (Off, On)
p4 Alarm type (Off, H, L, TH, TL)
p5 Alarm value exponent (100 to 999)
p6 Alarm value mantissa (-16 to 16)
p7 Detection (Off, On)
p8 Output (Off, DO, SW)
Off
DO
SW
p9 Number
If p8=DO
If p8=SW
IM 04L51B01-17EN
Output to a relay (DO
channel)
Output to an internal
switch
R e l a y ( D O c h a n n e l )
number
Internal switch number
(001 to 100)
Do Not Output Alarms
Output to a relay (DO
channel)
Output to an internal
switch
R e l a y ( D O c h a n n e l )
number
Internal switch number
(001 to 100)
Query
SAlarmMath[,p1[,p2]]?
Example Set a high limit alarm (H) on alarm number 2 of
math channel 015. Set the alarm value to 85.0.
When an alarm occurs, output to the relay (DO
channel) at number 0105.
SAlarmMath,015,2,On,H,850,On,
DO,0105
Description
You cannot set this on a "Off" channel.
If p3=Off, you cannot set p4 or subsequent
parameters.
If p7 (p8 for logarithmic math) = Off, you cannot set p8
(p9 for logarithmic math).
You cannot set DO channels or internal switches
whose output type is set to Manual as output
destination numbers.
SAlmHysMath
Alarm Hysteresis (/MT)
Sets the alarm hysteresis for a math channel.
Syntax
SAlmHysMath,p1,p2,p3
p1 Channel number
p2 Alarm number (1 to 4)
p3 Hysteresis
Alarm Type
H, L
Channel Using Logarithmic Math
Syntax
SAlmHysMath,p1,p2,p3,p4
p1 Channel number
p2 Alarm number (1 to 4)
p3 Hysteresis exponent (100 to 999)
p4 Hysteresis mantissa (-16 to 16)
Query
SAlmHysMath[,p1[,p2]]?
Example Set a hysteresis on alarm 3 of math channel
015.
SAlmHysMath,015,3,10
Description
Hysteresis specified for delay high and low limit
alarms (TH and TL) does not apply.
SAlmDlyMath
Alarm Delay Time (/MT)
Sets the alarm delay time for a math channel.
Syntax
SAlmDlyMath,p1,p2,p3,p4
p1 Channel number
p2 Hour (0 to 24)
p3 Minute (0 to 59)
P4 Second (0 to 59)
Query
SAlmDlyMath[,p1]?
Example Set the math channel 015 alarm delay time to
2 minutes 30 seconds.
SAlmDlyMath,015,0,2,30
Description
Set the delay time so that it is an integer multiple of
the scan interval
(SScan
2.4 Setting Commands
Hysteresis Range
0 to 100000
command).
2-35
1
2
App