2.4 Setting Commands
p5 Span lower limit
p6 Span upper limit
p7 Bias (–999999 to 999999)
p8 Decimal place (0 to 5)
p9 Scaling lower limit
p10 Scaling upper limit
p11 Unit (up to 6 characters, UTF-8)
p12 Low-cut function (Off, On)
p13 Low-cut point (0 to 50)
Square Root Channels
Syntax
SRangeAICurrent,p1,p2,p3,p4,p5,p6,
p7,p8,p9,p10,p11,p12,p13,p14
p1 Channel number
p2 Input type (Current, GS)
p3 Range
0-20mA
4-20mA
P4 Math type (Sqrt)
p5 Span lower limit
p6 Span upper limit
p7 Bias (–999999 to 999999)
p8 Decimal place (0 to 5)
p9 Scaling lower limit
p10 Scaling upper limit
p11 Unit (up to 6 characters, UTF-8)
p12 Low-cut function (Off, On)
p13 Low-cut point (0 to 50)
p14 Low-cut output (Zero, Linear)
Query
SRangeAICurrent[,p1]?
Example Measure 0.000 to 10.000 mA on channel 0002.
No scaling. No bias.
SRangeAICurrent,0002,Current,0-
20mA,Off,0,10000,0
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
If p2=GS, you cannot specify p4=Off/Delta.
Specify p5 and p6 within the range shown in the
following table.
Range (p3)
Value (p5, p6)
0-20mA
0.000 to 20.000
4-20mA
3.200 to 20.800
SRangePulse
Measurement Range of Pulse Input
Channel
Sets the measurement range of a pulse input channel.
Unused Channels
Syntax
SRangePulse,p1,p2
p1 Channel number
p2 Input type (Skip)
Channels Whose Input Type is PulseInput and No
Math
Syntax
SRangePulse,p1,p2,p3,p4,p5,p6,p7
2-24
When p2 = Current
When p2 = GS
p1 Channel number
p2 Input type (PulseInput)
p3 Range (LevelRange, ContactRange)
LevelRange
ContactRange Contact
p4 Chattering filter (On, Off)
p5 Math type (Off)
p6 Span lower limit
p7 Span upper limit
Channels Whose Input Type is PulseInput and Delta
Syntax
SRangePulse,p1,p2,p3,p4,p5,p6,p7
,p8
p1 Channel number
p2 Input type (PulseInput)
p3 Range (LevelRange, ContactRange)
LevelRange
ContactRange Contact
p4 Chattering filter (On, Off)
p5 Math type (Delta)
p6 Span lower limit
p7 Span upper limit
p8 Reference channel number
Channels Whose Input Type is PulseInput and Linear
Scaling
Syntax
SRangePulse,p1,p2,p3,p4,p5,p6,p7,p
8,p9,p10,p11
p1 Channel number
p2 Input type (PulseInput)
p3 Range (LevelRange, ContactRange)
LevelRange
ContactRange
p4 Chattering filter (On, Off)
p5 Math type (Scale)
p6 Span lower limit
p7 Span upper limit
p8 Decimal place (0, 1, 2, 3, 4, 5)
p9 Scaling lower limit
p10 Scaling upper limit
p11 Unit
Query
SRangePulse[,p1]?
Example Measure the pulse (level) on channel 0002.
Chattering filter is on. Math is on.
SRangePulse,0002,PulseInput,LevelR
ange,On,Off,0,1000,0,200,"m3/min"
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
Level
Level
Level
Contact