2.4 Setting Commands
SCtrlFilter
First-Order Lag Filter
Sets the first-order lag filter of the AI terminal of the PID
control module.
Syntax
SCtrlFilter,p1,p2,p3,p4,p5
p1 Unit number
p2 Module number
p3 AI terminal number (AI1, AI2)
p4 Enable or disable (On, Off)
p5 First-order lag constant (0 to 120) Unit:
sec
Query
SCtrlFilter[,p1,p2,p3]?
Example Set the first-order lag of AI1 of module number
2 connected to the main unit to 110 (s).
SCtrlFilter,0,2,AI1,On,110
Description
This command is valid when a PID Control Module is
installed.
SCtrlCalibAI
Calibration Correction
Sets the calibration correction of the AI terminal of the PID
control module.
Disable Calibration Correction
Syntax
SCtrlCalibAI,p1,p2,p3,p4
p1
Unit number
p2
Module number
p3
AI terminal number (AI1, AI2)
p4
Linearizer mode
Off
Use Calibration Correction (Linearizer approximation,
linearizer bias)
Syntax
SCalibIO,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10,p11,p12,p13,p14,p15,p16,p17,
p18,p19p,20p,p21,p22,p23,p24,p25,p
26,p27,p28,p29
p1
Unit number
p2
Module number
p3
AI terminal number (AI1, AI2)
p4
Linearizer mode
Appro
Bias
Number of segmental points (2 to 12)
p5
Input value of segmental point 1
p6
p7
Output value of segmental point 1
p8
Input value of segmental point 2
p9
Output value of segmental point 2
p10 Input value of segmental point 3 (number
of segmental points ≥ 3)
p11 Output value of segmental point 3
(number of segmental points ≥ 3)
p12 Input value of segmental point 4 (number
of segmental points ≥ 4)
p13 Output value of segmental point 4
(number of segmental points ≥ 4)
p14 Input value of segmental point 5 (number
of segmental points ≥ 5)
2-80
Correction is not
performed.
Linearizer approximation
Linearizer bias
p15 Output value of segmental point 5
(number of segmental points ≥ 5)
p16 Input value of segmental point 6 (number
of segmental points ≥ 6)
p17 Output value of segmental point 6
(number of segmental points ≥ 6)
p18 Input value of segmental point 7 (number
of segmental points ≥ 7)
p19 Output value of segmental point 7
(number of segmental points ≥ 7)
p20 Input value of segmental point 8 (number
of segmental points ≥ 8)
p21 Output value of segmental point 8
(number of segmental points ≥ 8)
p22 Input value of segmental point 9 (number
of segmental points ≥ 9)
p23 Output value of segmental point 9
(number of segmental points ≥ 9)
p24 Input value of segmental point 10
(number of segmental points ≥ 10)
p25 Output value of segmental point 10
(number of segmental points ≥ 10)
p26 Input value of segmental point 11
(number of segmental points ≥ 11)
p27 Output value of segmental point 11
(number of segmental points ≥ 11)
p28 Input value of segmental point 12
(number of segmental points ≥ 12)
p29 Output value of segmental point 12
(number of segmental points ≥ 12)
Use Calibration Correction (Correction coefficient)
Syntax
SCtrlCalibAI,p1,p2,p3,p4,p5,p6,p7,
p8,p9,p10,p11,p12,p13,p14,p15,p16,
p17,p18,p19p,20p,p21,p22,p23,p24,p
25,p26,p27,p28,p29,p30,p31,p32,p33
,p34,p35,p36,p37,p38,p39,p40,p41
p1
Unit number
Module number
p2
AI terminal number (AI1, AI2)
p3
Linearizer mode
p4
Correct
p5
Number of correction points (2 to 12)
p6
Uncorrected value 1
p7
Instrument correction coefficient 1
p8
Sensor correction coefficient 1
p9
Uncorrected value 2
p10 Instrument correction coefficient 2
p11 Sensor correction coefficient 2
p12 Uncorrected value 3 (number of
segmental points ≥ 3)
p13 Instrument correction factor 3 (number of
segmental points ≥ 3)
p14 Sensor correction factor 3 (number of
segmental points ≥ 3)
p15 Uncorrected value 4 (number of
segmental points ≥ 4)
p16 Instrument correction factor 4 (number of
segmental points ≥ 4)
p17 Sensor correction factor 4 (number of
segmental points ≥ 4)
p18 Uncorrected value 5 (number of
segmental points ≥ 5)
Correction Factor
IM 04L51B01-17EN