YOKOGAWA GX10 User Manual page 201

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

IM 04L51B01-17EN
Decimal Point Place (16 bits)
Indicates the decimal point place.
Bit
Value
Description
0 to 3
0 to 4
PV
4 to 7
0 to 4
SP
8 to 11
1
OUT
Alarm (32 bits)
Indicates the alarm status.
The eight bit values of alarm 1 to alarm 4 are described in the table below.
Bit
Value
Description
0 to 5
0
No alarm
1
High limit alarm
2
Low limit alarm
3
Difference high limit alarm
4
Difference low limit alarm
5
High limit on rate-of-change alarm
6
Low limit on rate-of-change alarm
7
Delay high limit alarm
8
Delay low limit alarm
6
0
No alarm is activated.
1
An alarm is activated.
7
0
Alarm nonhold state
1
Alarm hold state
R/S (8 bits)
Indicates the RUN or STOP of the control operation.
0: RUN, 1: STOP
A/M/C (8 bits)
Indicates the AUTO, MANUAL or CASCADE of the control operation.
0: AUTO, 1: MANUAL, 2: CASCADE
L/R (8 bits)
Indicates the LOCAL or REMOTE of the control operation.
0: LOCAL, 1: REMOTE
R/P/L (8 bits)
Indicates the RESET, PROGRAM or LOCAL of the control operation.
0: RESET, 1: PROG, 2: LOCAL
AT (8 bits)
Indicates the On or Off of the Auto tuning.
0: OFF, 1: ON
SPN (8 bits)
1 to 8: SP group number
PIDN (8 bits)
1 to 8: PID group number, 9: Reference PID
2.11 Format of the Data Block of Binary Output
1
2
App
2-183

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gm10Gx20Gp20Gp10

Table of Contents