SMltMultiKind
Multi Panel Type
Sets the multi panel pattern for multi batch.
Syntax
SMltMultiKind,p1,p2,p3,p4,p5
p1 Batch group number (1 to the number
used)
p2 Registration number (1 to 20)
p3 Screen position (1 to 6)
p4 Screen type (see p1 of the SMultiKind
command)
p5 Display group number
Query
SMltMultiKind[,p1[,p2[,p3]]]?
Example Set the panel of registration number 1 to "Split
2 Wide." Set the panel name to "Monitor1."
SMultiPattern,1,Wide2,'Monitor1'
Description
This command is valid for the GX20/GP20.
This command is valid when the multi batch function (/
BT) is enabled.
SBluetooth
Bluetooth Communication Function (/
C8) [GM]
Sets the Bluetooth communication function.
Syntax
SBluetooth,p1
p1 Bluetooth function On/Off (On, Off)
On
Off
Query
SBluetooth?
Example Use the Bluetooth communication function.
SBluetooth,On
Description
The settings specified with this command take effect
OBTApply
with the
command. The settings do not
change until you send the OBTApply command.
SBTID
Bluetooth Communication ID (/C8) [GM]
Sets the Bluetooth communication ID.
Syntax
SBTID,p1
p1 Local device name (GM's Bluetooth
device name)
Up to 30 characters, ASCII
Query
SBTID?
Example Set the local device name to "SMARTDAC+
GM."
SBTID,'SMARTDAC+ GM'
IM 04L51B01-17EN
Use
Not Use
SBTTimeOut
Bluetooth Communication Timeout (/C8)
[GM]
Sets the Bluetooth communication timeout.
Syntax
SBTTimeOut,p1
p1 Timeout function (Off, 1min, 2min, 5min,
10min)
Query
SBTTimeOut?
Example Set the Bluetooth communication timeout value
to 5 minutes.
SBTTimeOut,5min
Description
If the login function is in use, users that are logged in
are automatically logged out when a timeout occurs.
SUsbFunction
USB Communication Function [GM]
Configures USB communication function settings.
Syntax
SUsbFunction,p1
p1 USB communication function On/Off (On,
Off)
On
Off
Query
SUsbFunction?
Example Use the USB communication function.
SUsbFunction,On
Description
The settings specified with this command take effect
OUsbFApply
with the
command. The settings do not
change until you send the OUsbFApply command.
SUsbAutoLOut
USB Communication Auto Logout [GM]
Sets the auto logout for USB communication.
Syntax
SUsbAutoLOut,p1
p1 Auto logout function (Off, 1 min, 2 min, 5
min, 10 min)
Query
SUsbAutoLOut?
Example Set the USB communication's auto logout time
to 2 minutes.
SUsbAutoLOut,2min
Description
Users logged in via USB communication can be
automatically logged out.