2.4 Setting Commands
SAlarmIO
Alarm
Sets the alarm for an AI, DI, or PI channel.
Do Not Set Alarms
Syntax
SAlarmIO,p1,p2,p3
p1 Channel number
p2 Alarm number (1 to 4)
p3 Alarm on or off (Off)
Do Not Output Alarms
Syntax
SAlarmIO,p1,p2,p3,p4,p5,p6,p7
p1 Channel number
p2 Alarm number (1 to 4)
p3 Alarm on or off (On)
P4 Alarm type (H, L, DH, DL, RH, RL, TH, TL)
For a channel set to Log scale (/LG) (if p4
of SRangeAI is LogT1, LogT2, or LogT3),
p4 is H, L, TH, or TL.
p5 Value
For a channel set to Log scale (/LG) (if p4
of SRangeAI is LogT1, LogT2, or LogT3),
specify p5 using exponential notation (e.g.
1.23E10, where the number of digits of
the mantissa is as specified by p8 of the
SRangeAI command).
p6 Detection (Off, On)
p7 Output (Off)
Output Alarms
Syntax
SAlarmIO,p1,p2,p3,p4,p5,p6,p7,p8
p1 Channel number
p2 Alarm number (1 to 4)
p3 Alarm on or off (On)
P4 Alarm type (H, L, DH, DL, RH, RL, TH, TL)
For a channel set to Log scale (/LG) (if p4
of SRangeAI is LogT1, LogT2, or LogT3),
p4 is H, L, TH, or TL.
p5 Value
For a channel set to Log scale (/LG) (if p4
of SRangeAI is LogT1, LogT2, or LogT3),
specify p5 using exponential notation (e.g.
1.23E10, where the number of digits of
the mantissa is as specified by p8 of the
SRangeAI command).
p6 Detection (Off, On)
p7 Output
DO
SW
p8 Number
If p7=DO
If p7=SW
Query
SAlarmIO[,p1[,p2]]?
Example Set a high limit alarm (H) on alarm number 2 of
channel 0001. Set the alarm value to 1.8000V.
Use the alarm detection function. When an
alarm occurs, output to the relay (DO channel)
at number 0205.
2-28
Output to a relay (DO
channel)
Output to an internal switch
R e l a y ( D O c h a n n e l )
number
Internal switch number
(001 to 100)
SAlarmIO,0001,2,On,H,18000,On,DO,
0205
Description
You cannot set this on a "Skip" channel.
If p3=Off, you cannot set p4 or subsequent
parameters.
If p7=Off, you cannot set p8.
For the alarm values of p5, use the values in the
following table.
Channel
Input
Calculation
Type
Type
Type
AI channel Volt,
Off
GS,
Delta
TC,
Scale
RTD
Sqrt
LogT1
LogT2
LogT3
DI
Off
Delta
Scale
DI channel DI
Same as the DI input of AI channels
Pulse Off
PI channel Pulse Off
Delta
Scale
(1)
Within the measurement range
(2)
–5% to 105% of the scale but within –999999 to
999999 excluding the decimal point
(3)
1 digit to (measurement upper limit – measurement
lower limit)
(4)
1 digit to (scale upper limit – scale lower limit) but
within 1 to 999999 excluding the decimal point
(5)
Within the difference measurement range
(6)
Log scale range that corresponds to -5% to 105% of
the span
You cannot set DO channels or internal switches
whose output type is set to Manual as output
destination numbers.
You cannot set DI channels when the measurement
mode is set to high speed.
SAlmHysIO
Alarm Hysteresis
Sets the alarm hysteresis for an AI, DI, or PI channel.
Syntax
SAlmHysIO,p1,p2,p3
p1 Channel number
p2 Alarm number (1 to 4)
p3 Hysteresis
Alarm Type
H, L, DH, DL
Delta
Linear scaling,
Square root
Log scale
(/LG)
Alarm Type
H, L,
RH, RL DH, DL
TH, TL
(1)
(3)
(1)
(3)
(5)
(2)
(4)
(2)
(4)
(6)
0, 1
1
(1)
(3)
(5)
(2)
(4)
0 -
1 -
Off
999999
999999
(1)
(3)
(1)
(3)
(5)
(2)
(4)
Hysteresis Range
0.0% to 5.0% of the span or
scale width
However, this is fixed to 0
for DI channels.
0 to 5.0% of the measurement
range
0 to 100000
Fixed to 0.