YOKOGAWA GX10 User Manual page 91

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

SMasterScanGrp
Master Scan Interval
Sets the master scan interval when the measurement
mode is set to dual interval.
Syntax
SMasterScanGrp,p1
p1 Scan group number (1 or 2)
Query
SMasterScanGrp?
Example Set display group 5 to scan group 2.
SMasterScanGrp,2
Description
You can set this command when the dual interval
function is enabled.
SCtrlMode
Control Mode
Sets the control mode.
Syntax
SCtrlMode,p1,p2,p3,p4
p1 Unit number
p2 Module number
p3 Mode (Single, Cascade, PVSwitching)
Single
Cascade
PVSwitching
p4 PV switching condition (when p3 is
PVSwitching)
LowRange
HighRange
PVHigh
Signal
Query
SCtrlMode[,p1,p2]?
Example Set the control mode of the PID module with
module number 2, connected to the main unit,
to PV switching and the switching condition to
switch using DI.
SCtrlMode,0,2,PVSwitching,Signal
Description
This command is valid when a PID Control Module is
installed.
IM 04L51B01-17EN
SCtrlScan
Control Period
Sets the control period.
Syntax
Query
Example Set the control period to 100ms.
Description
SCtrlAction
Control
Sets the control.
Syntax
Single loop control
Cascade control
PV switching
Switch within range
(Low side)
Query
Switch within range
Example Set the power recovery action of module
(High side)
Switch at PV high
limit
Switch using DI
Description
SCtrlType
Control Type
Sets the control type.
Syntax
Query
Example Set the control type of loop number L022 to
Description
SCtrlScan,p1,p2,p3
p1 Unit number
Fixed to "–".
p2 Module number
Fixed to "–".
p3 Control period (100ms, 200ms)
SCtrlScan?
SCtrlScan,-,-,100ms
This command is valid when a PID Control Module is
installed.
SCtrlAction,p1,p2,p3
p1 Unit number
p2 Module number
p3 Power recovery action
RESTART_CONT
RESTART_MAN
RESTART_AUTO
RESTART_RESET
SCtrlAction[,p1,p2]
number 2 connected to the main unit to
manual.
SCtrlAction,0,2,RESTART_MAN
This command is valid when a PID Control Module is
installed.
You can set p3 to RESTART_RESET when the
program control function (/PG option) is enabled.
SCtrlType,p1,p2
p1 Loop number
p2 Control Type
PID
ONOFF
SCtrlType[,p1]?
ON/OFF control.
SCtrlType,L022,ONOFF
This command is valid when a PID Control Module is
installed.
2.4 Setting Commands
Continue
Manual
Auto
Reset
PID Control
ON/OFF control
2-73
1
2
App

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gm10Gx20Gp20Gp10

Table of Contents