2.4 Setting Commands
SSwitch
Internal Switch Operation
Sets the internal switch operation.
Syntax
SSwitch,p1,p2,p3,p4
p1 Internal switch number (1 to 100)
p2 Output type
Alarm
Manual Specify the output value
p3 Operation
And
Or
p4 Power supply
Last
On
Off
Query
SSwitch[,p1]?
Example Output an alarm on internal switch 3. Use "OR"
logic.
SSwitch,3,Alarm,Or
Description
p3 is valid when p2=Alarm.
p4 is valid when p2 is set to Manual.
SSerialBasic
Serial Communication Basics (/C2 or /
C3)
Sets basic serial communication parameters.
Not Use
Syntax
SSerialBasic,p1
p1 Function (Off)
Normal/Bar-code
Syntax
SSerialBasic,p1,p2,p3,p4,p5,p6,p7
p1 Function (Normal)
(GX/GP: Normal, Barcode, Darwin)
(GM: Normal, Darwin)
p2 Address (1 to 99)
p3 Baud rate [bps] (1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200)
P4 Parity (Odd, Even, None)
p5 Stop bits (1, 2)
p6 Data length [bit] (7, 8)
p7 Handshaking (Off:Off, XON;XON,
XON:RS, CS:RS)
Modbus Master and Modbus Slave
Syntax
SSerialBasic,p1,p2,p3,p4,p5
p1 Function (Master, Slave)
p2 Address (1 to 247)
p3 Baud rate [bps] (1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200)
P4 Parity (Odd, Even, None)
p5 Stop bits (1, 2)
Query
SSerialBasic?
2-52
Output alarms
Operate when all set alarms are
in the alarm state.
Operate when any of the set
alarms are in the alarm state.
Output the previous value
Output 1
Output 0
Example Set the baud rate to 9600, the data length to 8,
the parity check to ODD, the stop bits to 1, the
handshaking to OFF:OFF, the address to 02,
and the protocol to NORMAL.
SSerialBasic,Normal,2,9600,Odd,1,8
,Off:Off
Description
You can set p1=Master only on recorders that have the
/MC option.
The settings specified with this command takes effect
OSeriApply
with the
settings do not change until you send the OSeriApply
command.
For the communication commads that you can
execute using a bar-code reader, see section 1.18.11,
"Setting USB Input Devices (/UH option)" in the Model
GX10/GX20/GP10/GP20 Paperless Recorder User's
Manual (IM 04L51B01-01EN).
SModMaster
Modbus Master (/C2/MC or /C3/MC)
Sets the Modbus master operation.
Syntax
SModMaster,p1,p2,p3,p4,p5,p6
p1 Master function (Off, On)
p2 Read cycle (100ms, 200ms, 500ms, 1s,
2s, 5s, 10s, 20s, 30s, 1min)
p3 Communication timeout (100ms, 200ms,
250ms, 500ms, 1s, 2s 5s, 10s, 1min)
P4 Gap between messages (Off, 5ms, 10ms,
20ms, 50ms, 100ms)
p5 Recovery action: retransmission (Off, 1, 2,
3, 4, 5, 10, 20)
p6 Recovery action: wait time (Off, 5s, 10s,
30s, 1min, 2min, 5min)
Query
SModMaster?
Example Set the read cycle to 500ms, the
communication timeout to 250ms, the
gap between messages to 10ms, the
retransmission to 2, and the recovery wait time
to 5min.
SModMaster,On,500ms,250ms,2,5min