Communication Control Commands - YOKOGAWA GX10 User Manual

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

2.7
Communication
Control Commands
CCheckSum
Sets the Checksum
Sets the presence or absence of checksum.
Syntax
CCheckSum,p1
p1 Checksum usage
0
Do not compute
1
Compute
Query
Example Enable the checksum.
CCheckSum,1
CSFilter
Sets the Status Filter
Sets the filter used when outputting the recorder status.
Syntax
CSFilter,p1
p1 Filter values for status information
numbers 1 to 4 (0.0.0.0 to
255.255.255.255)
Query
CSFilter?
Example Set the status filter value to 255.127.63.31.
CSFilter,255.127.63.31
Description
The status filter is applied to each communication
connection.
CSFilterDB
Sets the status filter (expanded)
Sets the filter used when outputting the recorder status.
Syntax
CSFilterDB,p1,p2
p1 Filter values for status information
numbers 1 to 4 (0.0.0.0 to
255.255.255.255)
p2 Filter values for status information
numbers 5 to 8 (0.0.0.0 to
255.255.255.255)
Query
CSFilterDB?
Example Set the status filter value of status information
1 to 4 to 255.127.63.31 and that of status
information 5 to 8 to 1.2.3.4.
CSFilterDB,255.127.63.31,1.2.3.4
Description
The status filter is applied to each communication
connection.
p2 can be omitted.
IM 04L51B01-17EN
CLogin
Log in over a Communication Path
Logs in over a communication path.
Syntax
CLogin,p1,p2
p1 User name
p2 password
Example Log in using the user name "admin" and
password "password."
CLogin,admin,password
Description
For the characters that you can use for the password,
Appendix
1.
see
If this command is executed while logged in, the user
is once logged out and then logged back in.
When Using the Advanced Security Function (/AS)
Syntax
CLogin,p1,p2,p3,p4,p5
p1 User name
p2 User ID
p3 Password
p4 The new password when the password
has expired
p5 The new password when the password
has expired for confirmation
Example Log in using the user name "admin01" and
password "password01."
CLogin,admin01,,password01
Description
If p4 and p5 are not specified, normal login will be
used.
Even if the password has not expired, you can enter
a new password in p4 in p5 to change the password
and log in.
If p4 and p5 are not the same, an error will occur.
You cannot change to the same password (if p3 is the
same as p4 and p5, an error will occur).
If the user ID is not used, p2 is invalid.
When using the password management, you cannot
specify p4 and p5.
For the characters that you can use for the password,
Appendix
1.
see
If this command is executed while logged in, the user
is once logged out and then logged back in.
CLogout
Log Out over a Communication Path
Logs out over a communication path.
Syntax
CLogout
Example Logs out from the recorder.
CLogout
1
2
App
2-113

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gm10Gx20Gp20Gp10

Table of Contents