YOKOGAWA GX10 User Manual page 43

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

SRangeDI
Measurement Range of DI Channel
Sets the measurement range of a DI channel.
Unused Channels
Syntax
SRangeDI,p1,p2
p1 Channel number
p2 Input type (Skip)
Channels That Are Not Delta, Scaling, Pulse Input
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6
p1 Channel number
p2 Input type (DI)
p3 Fixed at "-."
P4 Calculation type (Off)
p5 Span lower limit (0 to 1)
p6 Span upper limit (0 to 1)
Delta Channels
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6,p7
p1 Channel number
p2 Input type (DI)
p3 Fixed at "-."
P4 Calculation type (Delta)
p5 Span lower limit (0 to 1)
p6 Span upper limit (0 to 1)
p7 Reference channel number
Scaling Channels
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10
p1 Channel number
p2 Input type (DI)
p3 Fixed at "-."
P4 Calculation type (Scale)
p5 Span lower limit (0 to 1)
p6 Span upper limit (0 to 1)
p7 Decimal Place (0 to 5)
p8 Scaling lower limit
p9 Scaling upper limit
p10 Unit (up to 6 characters, UTF-8)
Pulse Input Channels
Syntax
SRangeDI,p1,p2,p3,p4,p5,p6
p1 Channel number
p2 Input type (Pulse)
p3 Fixed at "-."
P4 Math type (Off)
p5 Span lower limit (0 to 999999)
p6 Span upper limit (0 to 999999)
Query
SRangeDI[,p1]?
Example Measure 0 to 1 on channel 0103. No scaling.
SRangeDI,0103,DI,-,Off,0,1
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
IM 04L51B01-17EN
p2=Pulse can be specified when the math function (/
MT) is installed.
If p2=Pulse, p4=Delta or Scale cannot be specified.
p2=Pulse cannot be specified when the operation
mode of the DI module is set to Remote.
You cannot use this command to configure settings
when the measurement mode is set to high speed.
SRangeDO
DO Channel Operation
Sets the DO channel operation.
Alarm Output
Syntax
SRangeDO,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1 Channel number
p2 Output type (Alarm)
p3 Span lower limit (0 to 1)
P4 Span upper limit (0 to 1)
p5 Unit (up to 6 characters, UTF-8)
p6 Energize or de-energize
Energize
De_Energize
p7 Operation
Operate when all set alarms are
And
in the alarm state.
Operate when any of the set
Or
alarms are in the alarm state.
p8 Hold or nonhold
Hold
Nonhold
p9 Relay (DO channel) action on
acknowledge (Normal, Reset)
Alarm Output (Reflash)
Syntax
SRangeDO,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1 Channel number
p2 Output type (Alarm)
p3 Span lower limit (0 to 1)
P4 Span upper limit (0 to 1)
p5 Unit (up to 6 characters, UTF-8)
p6 Energize or de-energize
Energize
De_Energize
p7 Action (Reflash)
p8 Reflash time (500ms, 1s, 2s)
p9 Relay (DO channel) action on
acknowledge
Manual Output
Specifies the output value.
2.4 Setting Commands
Energize the relay (DO
channel) during output.
De-energize the relay
(DO channel) during
output.
Hold output until an
alarm ACK operation.
Clear output when the
alarm is cleared.
Energize the relay (DO
channel) during output.
De-energize the relay
(DO channel) during
output.
2-25