YOKOGAWA GX10 User Manual page 75

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

SMailTime
Scheduled Transmission Times
Sets the scheduled transmission times.
Syntax
SMailTime,p1,p2,p3,p4
p1 Recipient (1 or 2)
p2 Reference time: Hours (HH) (00 to 23)
p3 Reference time: Minutes (MM) (00 to 59)
P4 Interval (1h, 2h, 3h, 4h, 6h, 8h, 12h, 24h)
Query
SMailTime[,p1]?
Example Send mail to recipient 1 every day at 08:30.
SMailTime,1,08,30,24
SSntpCnct
SNTP Client
Sets the SNTP client operation and the connection
destination server.
Syntax
SSntpCnct,p1,p2,p3,p4,p5,p6,p7
p1 Server name (up to 64 characters, ASCII)
p2 Port number (1 to 65535)
p3 Reference time: Hours (HH) (00 to 23)
P4 Reference time: Minutes (MM) (00 to 59)
p5 Access interval (6h, 12h, 24h)
p6 Timeout (10s, 30s, 90s)
p7 Time adjust on start action (Off, On)
Query
SSntpCnct?
Example Set the server name to "sntpserver1," the port
number to "123," the timeout to 30s. Query the
time every day at 12:00 and at memory start.
SSntpCnct,'sntpserver1',123,12,00,
24,30s,On
SModClient
Modbus Client Operation (/MC)
Sets the Modbus client operation.
Syntax
SModClient,p1,p2,p3,p4
p1 Read cycle (100ms, 200ms, 500ms, 1s,
2s, 5s, 10s 20s, 30s, 1min)
p2 Recovery wait time (Off, 5s, 10s, 30s,
1min, 2min, 5min)
p3 Keep connection (Off, On)
P4 Connection timeout [s] (1 to 10)
Query
SModClient?
Example Set the read cycle to 100ms, the recovery wait
time to Off, and the connection timeout to 1
second.
SModClient,100ms,off,on,1
Description
This command is valid on models with the /MC
communication channel option.
IM 04L51B01-17EN
SModCList
Modbus Client Connection Destination
Server (/MC)
Sets the Modbus client connection destination server.
Syntax
SModCList,p1,p2,p3
p1 Registration number
p2 Server name (up to 64 characters, ASCII)
p3 Port number (1 to 65535)
Query
SModCList[,p1]?
Example Assign server name "recorder1" and port
number "502" to registration number 1.
SModClient,1,'recorder1',502
SModCCmd
Modbus Client Transmission Command
(/MC)
Sets the Modbus client transmission command.
Syntax
SModCCmd,p1,p2,p3,p4,p5,p6,p7,p8
,p9
p1 Command number
p2 Command type
Off
Write
Read
p3 Server number (1 to 16)
P4 Unit number (1 to 255)
p5 Data type
BIT
INT16
UINT16
INT32_B
INT32_L
UINT32_B
UINT32_L
FLOAT_B
FLOAT_L
p6 Register (1 to 465535)
p7 Channel type
IO
Math
Com
p8 First channel
p9 Last channel
Query
SModCCmd[p1]?
Example Register the following command in command
number 2: read the 32-bit signed integer data
that is assigned to registers 30003 (upper 16
bits) and 30004 (lower 16 bits) in the server
device assigned to address 5 and unit number
1 into channel C002.
2.4 Setting Commands
Disable command
Write a value to a Modbus
register of another device.
Read a value from a Modbus
register of another device.
Bit String data
16-bit signed integer
16-bit unsigned integer
32-bit signed integer (big
endian)
32-bit signed integer (little
endian)
32-bit unsigned integer (big
endian)
32-bit unsigned integer (little
endian)
32-bit floating point (big
endian)
32-bit floating point (little
endian)
I/O channel
Math channel
Communication channel
2-57