YOKOGAWA GX10 User Manual page 103

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

SCtrlSP
SPNo Group Setting 2 (Target Setpoint
Alarm)
Sets the target setpoint
Syntax
SCtrlSP,p1,p2,p3
p1 Loop number
p2 Target setpoint number (1 to 8)
p3 Target setpoint (target setpoint low limit to
target setpoint high limit)
Query
SCtrlSP[,p1,p2]?
Example For loop number L022, set the target setpoint
of target setpoint number 8 to -2500.5.
SCtrlSP,L022,8,-25005
Description
This command is valid when a PID Control Module is
installed.
SCtrlSPGradient
SPNo Group Setting 3 (Target Setpoint
Ramp-Rate)
Sets the target setpoint ramp-rate
Syntax
SCtrlSPGradient, p1, p2,p3,p4,p5,p6
p1
Loop number
p2
Target setpoint number (fixed to "-")
p3
Target setpoint ramp-down rate
Off
On
p4
Target setpoint ramp-down rate value
0.0 + 1 digit to 100.0 (%) of the PV
range span
Example 0.1 to 100.0° (1 to 1000) when the
PV range is 0.0 to 100.0°
p5
Target setpoint ramp-up rate
Off
On
Target setpoint ramp-up rate value
p6
0.0 + 1 digit to 100.0 (%) of the PV
range span
Example 0.1 to 100.0° (1 to 1000) when the
PV range is 0.0 to 100.0°
Query
SCtrlSPGradient[,p1]?
Example For loop number L022, set the ramp-down rate
to 350.4 and the ramp-up rate to 580.9.
SCtrlSPGradient,L022,On,3504,
On,5809
Description
This command is valid when a PID Control Module is
installed.
IM 04L51B01-17EN
SCtrlPIDNo
SPNo Group Setting 4 (PID Group
Number)
Sets the target setpoint PID group number
Syntax
SCtrlPIDNo,p1,p2,p3
p1 Loop number
p2 Target setpoint number (1 to 8)
p3 PID group number (1 to 8)
Query
SCtrlPIDNo[,p1,p2]?
Example For loop number L022, set the PID group
number of target setpoint number 8 to 3.
SCtrlPIDNo,L022,8,3
Description
This command is valid when a PID Control Module is
installed.
The maximum value of p3 is the number of SP groups
SCtrlSPPID
set using p3 of the
SCtrlRefPoint
Zone PID Setting 1 (Reference Point)
Sets the zone PID reference point
Syntax
SCtrlRefPoint,p1,p2,p3
p1 Loop number
p2 Reference point number (1 to number of
PID groups – 1)
p3 Reference point (PV range low limit to PV
range high limit)
Query
SCtrlRefPoint[,p1,p2]?
Example For loop number L022, set the reference point
of reference point number 7 to -450.5.
SCtrlRefPoint,L022,7,-4505
Description
This command is valid when a PID Control Module is
installed.
SCtrlRHys
Zone PID Setting 2 (Switching
Hysteresis)
Sets the zone PID switching hysteresis
Syntax
SCtrlRHys,p1,p2
p1
Loop number
Switching hysteresis
p2
0% to 100% of PV range span
Example 0.0 to 100.0° (0 to 900) when the PV
range is 10.0 to 90.0°
Query
SCtrlRHys[,p1]?
Example For loop number L022, set the switching
hysteresis to 30.8.
SCtrlRHys,L022,308
Description
This command is valid when a PID Control Module is
installed.
2.4 Setting Commands