SPresetAO
Sets the Preset Action
Sets the preset action of an AO channel.
Syntax
SPresetAO,p1,p2,p3,p4
p1 Channel number
p2 Action at power-on (Last, Preset)
Last
Preset
p3 Action on error (Last, Preset)
Last
Preset
p4 Action on stop (Last, Preset)
Last
Preset
Query
SPresetAO[,p1]?
Example At power-on, replace the channel 0001 value
with the preset value of 0.5.
SPresetAO,0001,Preset,0.5
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
"Action on stop" indicates a scanning stopped, math
stopped, or re-transmission off condition.
SMathBasic
Math Action (/MT)
Sets the basic operation of math channels.
Syntax
GX/GP
SMathBasic,p1,p2,p3,p4,p5
GM
SMathBasic,p1,p2,p3,p4,p5,p6,p7
p1 Indication on computation error
+Over
-Over
p2 SUM and AVE computation when overflow
data is detected
Error
Skip
Limit
IM 04L51B01-17EN
Hold previous value
Output preset value
Hold previous value
Output preset value
Hold previous value
Output preset value
Display the computed
value as +Over.
Display the computed
value as -Over.
Sets the computation
result to computation
error.
Discards the data that
overflowed and continues
the computation.
Computes by substituting
upper or lower limit
values in the data that
overflowed.
For channels that do
not have linear scaling
specified, the upper
or lower limit of the
measuring range
For channels that
have linear scaling
specified, the scaling
upper or lower limit
p3 MAX, MIN, and P-P computation when
overflow data is detected
Over
Skip
P4 START/STOP key action
(GX/GP: Off, Start/Stop, Reset+Start/
Stop)
(GM: Off)
Off
Start/Stop
Reset+
Start/Stop
p5 PSUM over operation (GX/GP)
Rotate
Over
P5 START key action (Off, Start, Reset+Start)
(GM)
Off
Start
Reset+Start Computation resets and
P6 STOP key action (Off, Stop)
Off
Stop
p7 PSUM over operation (GM)
Rotate
Over
Query
SMathBasic?
Example Set the indication on computation error to
"+Over," computation when overflow data is
detected to "Skip," and start computation when
recording starts.
SMathBasic,+Over,Skip,Skip,Start/
Stop
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
p5 and p6 are invalid parameters for the GX/GP.
When the multi batch function (/BT) is enabled, p4 is
fixed to Off.
2.4 Setting Commands
For math channels,
the specified span
upper or lower limit.
Computes using data that
overflowed.
Discards the data that
overflowed and continues
the computation.
Computation does not
start even when recording
starts.
Computation starts when
recording starts.
Computation resets and
starts when recording
starts.
Rotate
Over
Recording starts but not
computation.
Computation starts when
recording starts.
starts when recording
starts.
Recording stops but not
computation.
Computation stops when
recording stops.
Rotate
Over
2-33