2.4 Setting Commands
SMail
Destination and Behavior for Each Mail
Type
Sets the destination and behavior for each mail type.
Alarm Notification
Syntax
SMail,p1,p2,p3,p4,p5,p6
p1 Setting type (Alarm)
p2 Recipient (Off, 1, 2, 1+2)
Off
1
2
1+2
p3 Inclusion of instantaneous data (Off, On)
P4 Alarm action
On
On+Off Send mails when alarms occur
p5 Inclusion of tag number or channel
number in subject (Off, On)
Scheduled Transmission
Syntax
SMail,p1,p2,p3
p1 Setting type (Time)
p2 Recipient (Off, 1, 2, 1+2)
p3 Inclusion of instantaneous data (Off, On)
Report Notification (/MT)
Syntax
SMail,p1,p2
p1 Setting type (Report)
p2 Recipient (Off, 1, 2, 1+2)
Media Alarm Notification
Syntax
SMail,p1,p2
p1 Setting type (Media)
p2 Recipient (Off, 1, 2, 1+2)
Power failure notification
Syntax
SMail,p1,p2
p1 Setting type (Power)
p2 Recipient (Off, 1, 2, 1+2)
System Error Notification
Syntax
SMail,p1,p2
p1 Setting type (System)
p2 Recipient (Off, 1, 2, 1+2)
User Lockout Notification (/AS)
Syntax
SMail,p1,p2
p1 Setting type (UserLock)
p2 Recipient (Off, 1, 2, 1+2)
Query
SMail[p1]?
Example Send alarm notifications to recipient 1 when
alarms occur and when they are cleared.
Include instantaneous data at the time of
transmission, and include the tag number or
channel number in the subject.
SMail,Alarm,1,On,On+Off,On
Description
The report function is an option (/MT).
2-56
Not send
Send to recipient 1
Send to recipient 1
Send to recipient 1 and 2
Send mails when alarms occur
and when they are cleared
SMailAlarm
Alarm Notification Mail Target Channels
Detects the alarm status of the specified channels and
sends alarm notifications.
Syntax
SMailAlarm,p1
p1 Channel string (up to 249 characters, up
to 50 channels)
Use channel number to specify the
channels. 4-digit numbers for I/O
channels. Numbers that start with "A"
for math channels (A015). Numbers
that start with "C" for communication
channels (C020). The maximum
number of characters per channel is 4.
Use periods to separate channel
numbers (see example).
To specify all channels from the first
channel to the last channel, delimit the
channels with a hyphen. An error will
occur if there are no valid channels in
the hyphen designated channels.
Query
SMailAlarm?
The channel string is output exactly as it is
specified.
Example Set the target channels to channels 0001 to
0021, 0101, A025, and C003.
SMailAlarm,'1-21.101.A25.C3'
SMailAlarmLevel
Alarm Notification Mail Target Alarm
levels
Detects the alarm status of the specified alarm levels and
sends alarm notification mails.
Syntax
SMailAlarmLevel,p1,p2,p3,p4
p1 Alarm level 1 (On, Off)
p2 Alarm level 2 (On, Off)
p3 Alarm level 3 (On, Off)
P4 Alarm level 4 (On, Off)
Query
SMailAlarmLevel?
Example Set the target alarm levels 1 and 2 to On, 3
and 4 to Off.
SMailAlarmLevel,On,On,Off,Off
SMailAlarmDetect
Alarm Notification Mail Target Alarm
Detection Method
Sets the alarm detection method for the alarm notification
mail.
Syntax
SMailAlarmDetect,p1
p1 Detection method (Ch, Level)
Query
SMailAlarmDetect?
Example Use alarm levels to specify the target alarms.
SMailAlarmDetect,Level
Description
When p1=Ch, use SMailAlarm command to
set the target channels. When p1=Level, use
SMailAlarmLevel command to set the target levels.