Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

2.4 Setting Commands
SCalibIO
Calibration Correction
Sets the calibration correction for AI channels.
Disable Calibration Correction
Syntax
SCalibIO,p1,p2
p1 Channel number
p2 Linearizer mode (Off)
Use Calibration Correction (Linearizer approximation,
linearizer bias)
Syntax
SCalibIO,p1
p1 Channel number
p2 Linearizer mode
Appro
Bias
p3 Number of set points (2 to 12)
P4 Input value of set point 1
p5 Output value of set point 1
p6 Input value of set point 2
p7 Output value of set point 2
p8 Input value of set point 3
p9 Output value of set point 3
p10 Input value of set point 4
p11 Output value of set point 4
p12 Input value of set point 5
p13 Output value of set point 5
p14 Input value of set point 6
p15 Output value of set point 6
p16 Input value of set point 7
p17 Output value of set point 7
p18 Input value of set point 8
p19 Output value of set point 8
p20 Input value of set point 9
p21 Output value of set point 9
p22 Input value of set point 10
p23 Output value of set point 10
p24 Input value of set point 11
p25 Output value of set point 11
p26 Input value of set point 12
p27 Output value of set point 12
Use Calibration Correction (Correction coefficient) (/
AH)
Syntax
SCalibIO,p1,p2,p3,p4,p5,p6,p7,p8,p
9,p10,p11,p12,p13,p14,p15,p16,p17,
p18,p19p,20p,p21,p22,p23,p24,p25,p
26,p27,p28,p29,p30,p31,p32,p33,p34
,p35,p36,p37,p38,p39
p1 Channel number
p2 Mode
Correct Correction coefficient
p3 Number of correction points (2 to 12)
p4 Input value of uncorrected value 1
p5 Instrument correction coefficient 1
p6 Sensor correction coefficient 1
p7 Input value of uncorrected value 2
p8 Instrument correction coefficient 2
p9 Sensor correction coefficient 2
p10 Input value of uncorrected value 3
p11 Instrument correction coefficient 3
p12 Sensor correction coefficient 3
p13 Input value of uncorrected value 4
p14 Instrument correction coefficient 4
p15 Sensor correction coefficient 4
2-32
Linearizer approximation
Linearizer bias
p16 Input value of uncorrected value 5
p17 Instrument correction coefficient 5
p18 Sensor correction coefficient 5
p19 Input value of uncorrected value 6
p20 Instrument correction coefficient 6
p21 Sensor correction coefficient 6
p22 Input value of uncorrected value 7
p23 Instrument correction coefficient 7
p24 Sensor correction coefficient 7
p25 Input value of uncorrected value 8
p26 Instrument correction coefficient 8
p27 Sensor correction coefficient 8
p28 Input value of uncorrected value 9
p29 Instrument correction coefficient 9
p30 Sensor correction coefficient 9
p31 Input value of uncorrected value 10
p32 Instrument correction coefficient 10
p33 Sensor correction coefficient 10
p34 Input value of uncorrected value 11
p35 Instrument correction coefficient 11
p36 Sensor correction coefficient 11
p37 Input value of uncorrected value 12
p38 Instrument correction coefficient 12
p39 Sensor correction coefficient 12
Query
SCalibIO[,p1]?
Example Set three set points on channel 0001
(measurement range: 0 to 1.0000 V). Set the
set points as follows: when the input value is 0
V, the output value is 0.0010 V; when the input
value is 0.5000 V, the output value is 0.5020
V; when the input value is 1.0000 V, the output
value is 0.9970 V.
SCalibIO,0001,Appro,3,0,10,5000,
5020,10000,9970
Description
If p2=Off, you cannot set p3 or subsequent
parameters.
You cannot specify set points beyond the number of
points specified by p3.
If the AI channel input type (p2 of SRangeAI) is set
to Skip or DI, you cannot specify anything other than
p2=Off.
IM 04L51B01-17EN