2.4 Setting Commands
P6 Enable or disable user ID (On, Off)
Query
SSecurity?
Example Use the login function when operating the
recorder directly or via communication. When
logged in, automatically log out if there is no
user activity for 5 minutes. The screen can be
changed even when logged out.
SSecurity,Login,Login,5min,On
Description
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
You cannot use this command to configure settings
when logged in as a user (when the user level is
User).
p1 cannot be set to Operate when the advanced
security function (/AS) is enabled.
p5 and p6 are valid when the advanced security
function (/AS) is enabled.
SKdc
Password Management (/AS)
Sets the password management.
Syntax
SKdc,p1,p2
p1 Enable disable password management
(On, Off)
p2 Root user password (between 6 and 20
characters, ASCII)
Query
SKdc?
Example Enable password management. Set the root
user password to "root3210."
SKdc,On,root3210
SOpePass
Password to Unlock Operation [GX/GP]
Sets the password that is used to release the operation
lock.
Syntax
SOpePass,p1
p1 Password (up to 20 characters, UTF-8)
Query
SOpePass?
The password is displayed using asterisks.
Example Set the password to "password1."
SOpePass,'password1'
Description
You cannot use this command to configure settings
when logged in as a user (when the user level is
User).
2-62
SOpeLimit
Operation Lock Details [GX/GP]
Sets which operations to lock.
Syntax
SOpeLimit,p1,p2
p1 Authority of user
Memory
Math
DataSave
Message
Batch
AlarmACK
Comm
DispOpe
ChangeSet Setting operation
DateSet
File
System
Out
CalibSet
CtrlIn
CtrlOut
Tuning
LocalSP
Program
p2 Free/Lock
Free
Not lock
Lock
Lock
Query
SOpeLimit[,p1]?
Example Prohibit operations for changing settings.
SOpeLimit,ChangeSet,Lock
Description
You cannot use this command to configure settings
when logged in as a user (when the user level is
User).
Memory
Computations
Data save
Message
Batch
Alarm ACK
Communication
Touch operation
Date/time settings
File operation
System operation
Output operation
Calibration correction
setting
(valid only when the
advanced security function
(/AS option) is in use on
instruments whose version
is 2.02 or later.)
Remote/Local operation
(This is valid when a PID
Control Module is installed.)
Control operation (same as
above)
Tuning operation (same as
above)
SP operation (same as
above)
Program operation (This is
valid when a PID Control
Module is installed and the
program control function (/
PG option) is in use.)