SFavoriteKind
Favorite Screen [GX/GP]
Set the favorite screen.
For Multi Panel
Syntax
SFavoriteKind,p1,p2,p3,p4,p5,p6
p1 Favorites number (1 to 20)
p2 Enable or disable (Off, On)
p3 Screen type (Multi)
p4 Multi panel number (1 to 20)
p5 Panel name (up to 16 characters, UTF-8)
p6 Batch group number (1 to the number
used)
p6 is valid when the multi batch function (/
BT) is enabled.
For Screens other than Multi Panel
Syntax
SFavoriteKind,p1,p2,p3,p4,p5,p6
p1 Favorites number (1 to 20)
p2 Enable or disable (Off, On)
p3 Screen type (see p1 of the
command)
P4 Display group number (when p3 is not
CustomDisplay)
Customized display screen number (1 to
30)
(when p3 is CustomDisplay)
Control group number (1 to 10)
(when p3 is ControlGroup)
Program pattern number (1 to 99)
(when p3 is ProgramSelect)
p5 Favorite screen name (up to 16
characters, UTF-8)
p6 Multi batch number (All, 1 to the number
used)
Query
SFavoriteKind[,p1]
Example Register the trend display of display group 2
to favorites screen number 1. Set the screen
name to "Favorite01."
SFavoriteKind,1,On,Trend,2,'Favori
te01'
Description
When the multi batch function (/BT) is not available,
p6 is fixed to 1.
p1 cannot be set to BatchOverview when p3 is 1 to
12.
P1 cannot be set to Trend, Digital, Bar, Alarm,
Message, Memory, or Multi when p3 = All.
ControlGroup, ControlSummary,
ControlAlarmSummary, ControlOverview, and Tuning
are valid when the PID control module is installed.
ProgramSelect and ProgramRun are options (/PG).
SMltTextField
Batch Text
Sets the batch text field for multi batch.
Syntax
SMltTextField,p1,p2,p3,p4
IM 04L51B01-17EN
Query
Example For field number 3 of batch group 2, set the
Description
This command cannot be used if the batch setting is
disabled (SBatch: p1=Off).
This command is the same as STextField when p1=1.
SMltFileHead
File Header
Sets the file header for multi batch.
Syntax
SHomeKind
Query
Example Set the batch group number to 1 and the file
Description
This command is the same as SFileHead when p1=1.
SMltFileName
File Naming Rule
Sets the file naming rule for saving multi batch data.
Syntax
Query
Example Set the file naming rule of batch group 2 to
Description
This command is the same as SFileName when p1=1.
If the batch setting is disabled (SBatch: p1=Off), p2
cannot be set to Batch.
2.4 Setting Commands
p1 Batch group number (1 to the number
used)
p2 Field number (1 to 24)
p3 Title (up to 20 characters, UTF-8)
p4 Character string (up to 30 characters,
UTF-8)
SMltTextField[,p1[,p2]]?
field title to "OPERATOR" and the character
string to "RECORDER1."
SMltTextField,2,3,'OPERATOR','RECO
RDER1'
SMltFileHead,p1,p2
p1 Batch group number (1 to the number
used)
p2 File header (up to 50 characters, UTF-8)
SMltFileHead[,p1]?
header to "GX_DATA."
SMltFileHead, 1, 'GX_DATA'
SMltFileName,p1,p2,p3
p1 Batch group number (1 to the number
used)
p2 File naming rule
Date
Date
Serial
Serial number
Batch
Batch name
p3 Specified file name (up to 16 characters,
ASCII)
SMltFileName[,p1]?
"Date."
Set the specified file name to "Recorder1_
data."
SMltFileName,2,Date,'Recorder1_
data'