YOKOGAWA GX10 User Manual page 81

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

SUser
User Settings
Register users.
Syntax
SUser,p1,p2,p3,p4,p5,p6,p7
p1 User number
p2 User level
Off
Admin
User
p3 Login mode
(GX/GP: Key, Comm, Key+Comm)
(GM: Comm)
Key
Comm
Key+Comm
P4 User name (up to 20 characters, ASCII)
p5 Password (up to 20 characters, ASCII)
p6 Enable or disable user limitation (Off, On)
p7 User limitation number (1 to 10)
Query
SUser[,p1]?
The password of p5 are displayed using
asterisks.
Example Register a user-level user to user number
3. Set the user name to "user10" and the
password to "pass012." Allow login only using
touch operation, and specify user limitation
number 5.
SUser,3,User,Key,'user10','pass012
',On,5
Description
If p1=1, p2 is fixed to Admin. In addition, you cannot
set p3 to Comm on the GX/GP.
If p2=Admin, p6 is fixed to Off.
You cannot enter NULL or spaces in p4 or p5.
For the characters that you can use in the specified
Appendix
password (p5), see
You cannot use this command to configure settings
when logged in as a user (when the user level is
User).
When Using the Advanced Security Function (/AS)
Syntax
SUser,p1,p2,p3,p4,p5,p6,p7,p8,p9,p
10,p11
p1 User number
p2 User level
Off
Admin
User
Monitor
p3 Login method
Key
Comm
Key+Comm
IM 04L51B01-17EN
Not Use
Administrator level
User level
Log in using touch operation
Log in via communication
(including Web)
Log in using touch operation
and via communication.
1.
Not use
Administrator level
User level
Monitor level
Log in using touch operation
Log in via communication
commands (including Web)
Log in using touch operation
and via communication.
P4 User name (up to 20 characters, ASCII)
p5 Password (between 6 and 20 characters,
ASCII)
p6 Enable or disable user limitation (Off, On)
p7 User limitation number (1 to 10)
p8 User ID (up to 20 characters, ASCII)
Specify a user ID and password
combination that have not been registered
in the past.
p9 Password expiration (Off, 1Month,
3Month, 6Month)
p10 Enable or disable sign in property (Off,
On)
p11 Sign in property number (1 to 8)
Query
SUser[,p1]?
The password of p5 and user ID of p8 are
displayed using asterisks.
Example Register a user-level user to user number 3.
Set the user name to "user10." Allow login
only using touch operation, and specify user
limitation number 5.
SUser,3,User,Key,'user10',,On,5
Description
If p1=1, p2 is fixed to Admin. In addition, you cannot
set p3 to Comm.
If p2=Admin, p6 and p10 are fixed to Off.
If p2=Monitor, p6, p9, and p10 are fixed to Off.
You cannot enter NULL or spaces in p4 or p5.
Setting to enable password management (SKdc
command)
• If p2=Off, Admin, or User, p5 is invalid. The response
to a query will be blank.
• p9 is fixed to Off.
You can specify p5 only when p2=Monitor.
When p2=Admin or User, you cannot specify p5
and the default password is enabled. For the default
password, see section 2.3.1, "Logging In" in the Model
GX10/GX20/GP10/GP20 Advanced Security Function
(/AS) User's Manual (IM 04L51B01-05EN) or section
2.3.1, "Logging In" in the Data Acquisition System GM
Advanced Security Function (/AS) User's Manual (IM
04L55B01-05EN).
For the characters that you can use in the specified
Appendix
password (p5), see
You cannot use this command to configure settings
when logged in as a user (when the user level is
User).
2.4 Setting Commands
1.
2-63
1
2
App

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gm10Gx20Gp20Gp10

Table of Contents