YOKOGAWA GX10 User Manual page 97

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

p9 Bias (–999999 to 999999)
p10 Decimal Place (0 to 5)
p11 Scaling low limit
p12 Scaling high limit
p13 Unit (up to 6 characters, UTF-8)
p14 Low-cut function (Off, On)
p15 Low-cut point (0 to 50)
p16 Low-cut operation mode (Zero, Linear)
Query
SCtrlRangeAI[,p1.p2,p3]?
Example Measure -0.5000 to 1.0000 V on channel 0002.
No scaling. No bias.
SCtrlRangeAI,0002,Volt,2V,O
ff,–5000,10000,0
Description
This command is valid when a PID Control Module is
installed.
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
If p4=TC/RTD, p6 is set to Off.
If p4=TC/RTD/DI, p6 cannot be set to Sqrt.
If p4=Volt/GS/DI, p6 cannot be set to Off.
If p4=DI, you cannot set p9 (bias).
For electromagnetic relay type or low withstand
voltage relay type analog input modules, p2 cannot be
set to RTD.
The settable items for p5 are shown in the table
below.
p4=Volt p4=TC
p4=RTD
20mV
R
Pt100
60mV
S
Pt100-H
200mV
B
JPt100
1V
K
JPt100-H
2V
K-H
Cu10GE
6V
E
Cu10LN
20V
J
Cu10WEED
50V
T
Cu10BAILEY
N
Cu10a392
W
Cu10a393
L
Cu25
U
Cu53
PLATINEL
Cu100
PR20-40
J263B
WRe3-25
Ni100SAMA
KpvsAu7Fe
Ni100DIN
NiNiMo
Ni120
WWRe26
Pt25
N14
Pt50
XK
Pt200WEED
Cu10G
Cu50G
Cu100G
Pt46G
Pt100G
For the setting ranges of p7 (span low limit) and p8
(span high limit), see the PID Control User's Manual
(IM 04L51B01-31EN).
SCtrlBurnOut
Burnout Mode
Sets the burnout action of the AI terminal of a PID module.
Syntax
SCtrlBurnOut,p1,p2,p3,p4
p1 Unit number
IM 04L51B01-17EN
Query
Example When a burnout is detected on AI1 of module
Description
This command is valid when a PID Control Module is
installed.
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
SCtrlRjc
RJC temperature
Sets the RJC temperature of the AI terminal of a PID
control module.
Syntax
p4=GS
p4=DI
1-5V
Level
0.4-2V
DI
Query
Example
Description
This command is valid when a PID Control Module is
installed.
You cannot use this command to configure settings
while recording is in progress.
You cannot use this command to configure settings
while computation is in progress.
If p4=Internal, you cannot set p5.
Absolute temperature (K) is valid when the input type
is TC and the range type is KpvsAu7Fe.
2.4 Setting Commands
p2 Module number
p3 AI terminal number (AI1, AI2)
p4 Burnout action (Off, Up, Down)
SCtrlBurnOut[,p1,p2,p3]?
number 2 connected to the main unit, set the
terminal to UP.
SBurnOut,0,2,AI1,Up
SCtrlRjc,p1,p2,p3,p4,p5
p1 Unit number
p2 Module number
p3 AI terminal number (AI1, AI2)
p4 Mode (Internal, External)
Internal
Internal
External
External
p5 Compensation temperature
Fahrenheit
-40 to 1760
Celsius
-200 to 800
Absolute
2531~3532
temperature
SCtrlRjc[,p1,p2,p3]?
Set the reference junction compensation of
AI1 of module number 2 connected to the
main unit to internal compensation circuit.
SCtrlRjc,0,2,AI1,Internal
Set the reference junction compensation
of AI1 of module number 2 connected to
the main unit to external reference junction
compensation and the compensation
temperature to -2.3.
SCtrlRjc,0,2,AI1,External,-23
1
2
App
2-79