Table 7-1 Installation And Wiring Checklist - Siemens SIMATIC FM 453 Manual

Servo drive / step drive positioning module
Hide thumbs Also See for SIMATIC FM 453:
Table of Contents

Advertisement

Starting up the FM 453
7.1
Installation and Wiring
Installation
You can find information about how to install your module:
Information
Wiring Information
You can find information about how to wire your module:
Checklist
The checklist below will help you check important steps in the installation
and parameterization of the FM 453 positioning module.
Table 7-1
Installation and Wiring Checklist
Step
Check
1
Slots
2
Shielding
3
Hardware limit
switches
4
Parameterize
7-2
In Chapter 3 of this manual
In the manual S7-400/M7-400 Programmable Controller, Hardware and
Installation
In Chapter 4 of this manual
In the manual S7-400/M7-400 Programmable Controller, Hardware and
Installation
Plug the module into one of the suitable slots.
Check the shielding of the FM 453 positioning module:
To ensure proper shielding, the module must be screwed down firmly
on the rack.
The shielding for shielded lines must be connected to the shielding termi-
nal element.
The shielding for the setpoint cable should not be grounded on the drive-
unit end.
Check the start/stop hardware limit switches. The hardware limit switch con-
nections must be connected to the power section. The start/stop hardware
limit switches should not be connected to the digital inputs.
Make sure the FM 453 positioning module setup is consistent with the para-
meterization. Check in particular that:
The attached encoder matches the machine data.
The wiring of the digital I/O modules matches the machine data.
What to Do:
FM 453 Servo Drive / Step Drive Positioning Module
C79000-G7076-C453-01
OK

Advertisement

Table of Contents
loading