Siemens Simovert 6SE70 Series Operating Instructions Manual

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
s
SIMOVERT Master Drives
Rectifier/Regenerating Unit
Sizes C to K
Edition: i
AoteWell LTD
AoteWell Automation Sales Team
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Operating Instructions
Order No.: 6SE7087-6AK85-1AA0
https://www.aotewell.com

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Simovert 6SE70 Series

  • Page 1 AoteWell Automation Sales Team Sales@aotewell.com Operating Instructions SIMOVERT Master Drives Rectifier/Regenerating Unit Sizes C to K Edition: i Order No.: 6SE7087-6AK85-1AA0 AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 2 The information given in this publication is reviewed at regular intervals and any corrections that might be necessary are made in the subsequent printings. Suggestions for improvement are welcome at all SIMOVERT ® is a registered trademark of Siemens times. © Siemens AG 1994 All rights reserved AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com...
  • Page 3: Table Of Contents

    Start-up with 12-pulse mode ....................3-57 3.8.6 Redundancy mode ....................... 3-59 3.8.7 RS485 interface cable for the peer-to-peer link on SST2 ............ 3-60 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 4 Download or upread (P052 = 3) ..................4-39 4.3.9.4 Hardware configuration (P052 = 4) ................... 4-40 4.3.9.5 Drive setting (P052 = 5) ....................4-41 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 5 Analog input/output ......................5-27 5.12 Communications ........................5-29 5.13 Diagnostics ........................... 5-34 5.14 Modulator ..........................5-36 5.15 Factory parameters ......................5-37 5.16 Profile parameters ........................ 5-38 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 6 Connection of rectifier/regenerating unit to a PC ..............9-8 9.7.3 Creating an online link to the rectifier/regenerating unit ............9-9 9.7.4 Further information ........................ 9-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 7 Power reduction at increased coolant temperature ............. 14-10 14.2 Power reduction at altitudes > 1000m above MSL .............. 14-10 14.3 Applied standards ........................ 14-11 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 8: Contents

    AoteWell Automation Sales Team Sales@aotewell.com Contents 09.02 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 9: Definitions

    You can consult your local Siemens branch if you should require further information or if particular problem occur that are not dealt with in adequate detail in the operating instructions.
  • Page 10 ESD coat ESD desk ESD armband ESD shoes earthing terminal on cabinets Sitting position Standing position Standing / Sitting position 0-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 11 Such personnel must be thoroughly acquainted with all warnings and maintenance activities. Perfect and safe operation of the equipment requires proper transport, expert storage, installation and assembly and cautious operation and maintenance. 0-11 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 12 AoteWell Automation Sales Team Sales@aotewell.com Definitions 09.02 0-12 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 13: Description

    Once the DC link capacitors have been precharged, the inverters are ready for operation. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 14 Optional interfaces and intelligent I/O modules are available in conjunction with programmable controllers and other automation equipment for controlling the rectifier/regenerating units. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 15: Transport, Unpacking And Assembly

    ♦ dimension drawing (Figure 2.4 for size H) The following are required for securing size K: ♦ six M8 bolts ♦ dimension drawing (Figure 2.5 for size K) Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 16 In the case of units of size H and K, all plastic covers must be mounted to ensure correct air flow and cooling for the units. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 17: Dimension Drawings

    AoteWell Automation Sales Team Sales@aotewell.com 05.00 Transport, Unpacking and Assembly Dimension drawings Figure 2.2 Dimension drawing, size C Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 18 AoteWell Automation Sales Team Sales@aotewell.com Transport, Unpacking and Assembly 05.00 Figure 2.3 Dimension drawing, size E Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 19 AoteWell Automation Sales Team Sales@aotewell.com 05.00 Transport, Unpacking and Assembly Figure 2.4 Dimension drawing, size H Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 20 AoteWell Automation Sales Team Sales@aotewell.com Transport, Unpacking and Assembly 05.00 Figure 2.5 Dimension drawing, size K Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 21 Rect. connection 6SE7034-6EE85-1AA0 6SE7033-5FE85-1AA0 6SE7034-2FE85-1AA0 6SE7031-4HE85-1AA0 Busbar 6SE7032-2HE85-1AA0 6SE7032-7HE85-1AA0 Regen. connection 6SE7036-1EE85-1AA0 6SE7034-2HE87-3AE0 6SE7035-4FE85-1AA0 6SE7034-2HE85-1AA0 Figure 2.8 Line connection w/o autotransformer (size E) Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 22 AoteWell Automation Sales Team Sales@aotewell.com Transport, Unpacking and Assembly 05.00 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 23: Connection

    An external 24 V power supply is required for operation of the units (see Chapters 3.5 and 9.3). Operational range of the unit: 20 V to 30 V. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 24: Power Connections

    Mains connection size H 1) Due to the press-in nuts, cable lugs or DC rails can only be connected to the terminal rails from the front. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 25 Output reactors in the DC circuit are not permitted (even with the parallel connection of power sections or in 12-pulse mode), because the DC link voltage is measured at the unit output terminals. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 26 The connection between the protective ground and electronic ground is interrupted (see Chapter 3.3.3 Terminals on the CUR Module). ● The rectifier/regenerating unit is operated in an ungrounded network. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 27 2) American Wire Gauge 3) Terminal connection area: Multicore10mm to 50mm AWG 8 to AWG 1/0 Stranded 3.5mm to 35mm AWG 12 to AWG 2 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 28 C 6x300 6x600 C 4x300 4x600 R 100x10 R 100x10 R 100x10 Table 3.2 Connection cross-sections 1) C=Cable, R=Rail 2) American Wire Gauge Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 29 Line protection must be ensured for all device types by assigning a suitable line protection element (e.g. fuse, line protection circuit-breaker) to the line cross-sectional area as defined in the currently valid standards – e.g. DIN VDE 0100 Part 430. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 30 32-7HE85-1AA0 350 3NE3231 170M4694 34-2HE85-1AA0 560 3NE3335 170M5697 35-3HE85-1AA0 710 3NE3337-8 170M5699 Table 3.4 Built-in DC link fuse 1) Not a US standard Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 31: Short-Circuit Withstand Capability For Sizes H And K

    =85 kA The power rails must be mechanically buffered to absorb the short-circuit forces directly in front of their entry point into the unit. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 32 500 / 50 41-0FH85-1AA0 500 to 600 4EU4351-5UA00 500 / 50 41-3FK85-1AA0 500 to 600 1119 1235 4EU4551-1UA00 500 / 50 1120 3-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 33 50/60 4BU4595-0UA11-8A 4AU3995-0UA61-8A 440-480 4BU4595-0UA21-8A 4AU3995-0UB01-8A 33-1EE85-1AA0 380-415 50/60 4BU4795-0UA01-8A 4BU4395-0UA41-8A 440-480 4BU4795-0UA11-8A 4BU4395-0UA51-8A 33-8EE85-1AA0 380-415 50/60 4BU5295-0UA01-8A 4BU4595-0UA61-8A 440-480 4BU5195-0UA01-8A 4BU4595-0UA71-8A 3-11 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 34 4BU5395-0UA21-8A 4BU4795-0UA81-8A 4BU5495-0UA51-8A 4BU4795-0UA41-8A 35-4FE85-1AA0 50/60 4BU5595-0UA01-8A 4BU5195-0UA51-8A 4BU5595-0UA51-8A 4BU5195-0UA21-8A 37-7FH85-1AA0 50/60 4BU5895-0UA21-8A 4BU5495-0UA41-8A 4BU5895-0UA71-8A 4BU5395-0UA41-8A 41-0FH85-1AA0 50/60 4BU6095-0UA11-8A 4BU5595-0UA41-8A 4BU5995-0UA31-8A 4BU5595-0UA21-8A 3-12 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 35 660-690 50/60 4BU6495-0UA11-8A 4BU6095-0UA31-8A 41-8HK85-1AA0 1633 1803 660-690 50/60 4BU6595-0UA01-8A 4BU6295-0UA41-8A 41-8HK85-1AD0 1633 1803 660-690 50/60 4BU6595-0UA01-8A 4BU6295-0UA41-8A Table 3.7 Recommended autotransformers 3-13 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 36: Power Supply And Main Contactor

    The main contactor’s operating coil must be protected, for example, by RC elements (Chapter 9). See also Warnings in Chapter 3.1 after Table 3.1 with regard to isolating transformer feed-in. 3-14 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 37: Control Terminal Block And Serial Interface

    Handling of these clamps is shown in Figure 3.6. If they intersect, control and power cables must be run at an angle of 90° to each other. 3-15 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 38: Terminals And Setting Elements On The Cur (A10) Module

    Terminals and setting elements on the CUR (A10) module R135 X100 X101 X102 R136 X104 Figure 3.7 Control terminals and setting elements on the CUR 3-16 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 39 Actual current value: 0V - ±5V corresponds to 0A - ± rated DC current Display range: 0 - ±10V, max. 5mA load, current limited 3-17 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 40: Connecting-Up The Parameterizing Unit (Pmu)

    Transmit- and receive line RS485, two-wire, negative differential input/output Ref. potential for RS232 or RS485 interface Table 3.10 Connector pin assignment for interface X300 3-18 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 41: Measures For Keeping To Rfi Suppression Regulations

    See also "SIMOVERT MASTERDRIVES Installation instructions for design of drives in conformance with EMC regulations“ under "Documentation" on the DriveMonitor CD-ROM of the inverter or converter "compendium" Chapter 3. 3-19 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 42: Single-Line Diagrams With Suggested Circuit Arrangements

    AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Single-line diagrams with suggested circuit arrangements Figure 3.9 Single-line diagram with suggested circuit arrangement without autotransformer, Size C 3-20 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 43 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.10 Single-line diagram with suggested circuit arrangement with autotransformer, Size C 3-21 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 44 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.11 Single-line diagram with suggested circuit arrangement without autotransformer, Size E 3-22 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 45 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.12 Single-line diagram with suggested circuit arrangement with autotransformer, Size E 3-23 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 46 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.13 Single-line diagram with suggested circuit arrangement without autotransformer, Size H 3-24 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 47 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.14 Single-line diagram with suggested circuit arrangement with autotransformer, Size H 3-25 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 48 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.15 Single-line diagram with suggested circuit arrangement without autotransformer, Size K 3-26 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 49 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.16 Single-line diagram with suggested circuit arrangement with autotransformer, Size K 3-27 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 50: Power Sections

    AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Power sections Figure 3.17 Power section, 6SE7022-1EC85-1AA0, 6SE7024-1EC85-1AA0 and 6SE7028-6EC85-1AA0,(380-480V / 21A, 41A and 86A) 3-28 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 51 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.18 Power section, 6SE7031-7EE85-1AA0 (380-480V / 173A) 3-29 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 52 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.19 Power section, 6SE7032-2EE85-1AA0 (380-480V / 222A) 3-30 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 53 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.20 Power section, 6SE7033-1EE85-1AA0 (380-480V / 310A) 3-31 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 54 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.21 Power section, 6SE7033-8EE85-1AA0 and 6SE7034-6EE85-1AA0 (380-480V / 375A and 463A) 3-32 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 55 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.22 Power section, 6SE7036-1EE85-1AA0 (380-480V / 605A) 3-33 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 56 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.23 Power section, Size H 3-34 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 57 Level B (rear level) Level A (front level) Figure 3.24 Arrangement of the thyristor blocks, Size H (see dimension drawing in Section 2.4) 3-35 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 58 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.25 Power section, Size K 3-36 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 59 Level B Figure 3.26 Arrangement of the thyristor blocks, view from right-hand side of unit, Size K (see dimension drawing in Section 2.4) 3-37 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 60 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.27 Power section, 6SE7022-7FC85-1AA0, 6SE7024-1FC85-1AA0, 6SE7027-2FC85-1AA0 and 6SE7028-8FC85-1AA0 (500-600V / 27A, 41A, 72A and 94A) 3-38 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 61 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.28 Power section, 6SE7031-5FE85-1AA0 (500-600V / 151A) 3-39 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 62 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.29 Power section, 6SE7032-4FE85-1AA0 (500-600V / 235A) 3-40 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 63 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.30 Power section, 6SE7032-7FE85-1AA0, 6SE7033-5FE85-1AA0, and 6SE7034-2FE85-1AA0 (500-600V / 270A, 354A and 420A) 3-41 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 64 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.31 Power section, 6SE7035-4FE85-1AA0 (500-600V / 536A) 3-42 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 65 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.32 Power section, 6SE7031-4HE85-1AA0 (660-690V / 140A) 3-43 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 66 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.33 Power section, 6SE7032-2HE85-1AA0 (660-690V / 222A) 3-44 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 67 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.34 Power section, 6SE7032-7HE85-1AA0 and 6SE7034-2HE85-1AA0 (660-690V / 270A and 420A) 3-45 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 68 AoteWell Automation Sales Team Sales@aotewell.com Connection 09.02 Figure 3.35 Power section, 6SE7035-3HE85-1AA0 (660-690V / 536A) 3-46 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 69: Parallel Connection Of Parallel Unit(S), Size K

    C98043- C98043- C98043- A1695 A1695 A1685 Figure 3.36 Connection of firing pulse signals and monitoring signals for the parallel units 3-47 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 70: Spare Parts

    50 mm in diameter (to allow the plug to be fed through). 3-48 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 71 On parallel connection the rating of the relay contact K1-2 (connection X9-4, X9-5) should be taken into account (refer to Chapter 3.2). 3-49 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 72: Single-Line Diagrams With Suggested Circuit Arrangements For Parallel Connection

    Single-line diagrams with suggested circuit arrangements for parallel connection Figure 3.37 Single-line diagram with suggested circuit for parallel connection without autotransformer, size K 3-50 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 73 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Connection Figure 3.38 Single-line diagram with suggested circuit for parallel connection with autotransformer, size K 3-51 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 74: 12-Pulse Mode (Only Possible With The Optional Rs485 Interface)

    • With Ud reduction, current asymmetry (as a result of a control angle of 0 degrees and differing voltage levels) can be prevented or considerably reduced. • An output reactor must not be used in the DC link. 3-52 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 75 Regeneration Mains X117 DC link X117 Reactor 12-pulse slave Rectification Regeneration Figure 3.40 Power section supply with autotransformers, reduced DC link voltage 3-53 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 76: Parameterization For 12-Pulse Mode

    Selection of the basic or reserve setting (index i001 or i002) of the appropriate "Source selection parameter“ (P554, P555, ...) is described in Section 4.1.2. 3-54 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 77 12-pulse transformer) from the delta winding of the 12-pulse transformer) Table 12 Parameterization for 12-pulse mode 3-55 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 78: Control/Status Word For 12-Pulse Mode (R599) And Control Word 2, Bit 23

    (No external fault 1) Table 13 Control/status word for 12-pulse mode (r599) 3-56 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 79: Start-Up With 12-Pulse Mode

    (index i002) is used to operate the unit as a stand-alone unit with user control on-site via the OP1S or PMU. 3-57 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 80 2 is a source for "No external warning 1". If this is not required, e.g. in the case of open terminals, P575 = 1 and P588 = 1 must be set. 3-58 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 81: Redundancy Mode

    6-pulse mode with external control. The Peer-to-Peer telegram failure monitoring time also has to be switched off via P687.i003= 0 in this case. 3-59 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 82: Rs485 Interface Cable For The Peer-To-Peer Link On Sst2

    12-pulse master 12-pulse slave X117 X117 Figure 3.42 Connecting cable for "Peer-to-Peer" communication on SST2 (between the terminals of the A2 submodule (C98043-A1690)) 3-60 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 83: Start-Up

    P571 = 1004 Selection of reduction via terminal X101-12 P613 = 1001 Output "DC Link voltage reduced" message to signaling relay X104-17/18 P319 Hysteresis "Link voltage reduced" message Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 84: Rectifier/Regenerating Unit

    - Operator control panel (OP) - Serial interfaces Only: Id setpoint in e.g. output current (SST1, SST2, SCB, CB, TB) 12-pulse operation Rectifier/regenerating unit Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 85 Affected parameters: P140 to P144, P160, P161, P310 to P320, P329, P408, P517, P518, P773 to P777 Used, e.g. for alternating operation of different inverter types on one rectifier/regenerating unit Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 86: Initial Start-Up

    A detailed description of the displays as well as the parameterizing and operator control possibilities of the rectifier/regenerating unit via the PMU, is provided in Section 6 "operator control". Parameterization is realized according to Sections 4.2.2 and 4.2.3 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 87: Parameterization "Standard Application

    80% of 1.35 x system voltage at the rectifier bridge 1) P571 = 0001 permanent selection of reduced voltage 1) P318 is not displayed in "standard mode" Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 88: Logbook

    DC link voltage) on the connected SIMOVERT Master Drive FC the dynamic behavior of the closed-loop control of the DC link voltage can be improved. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 89: Parameterization For "Expert Application

    (factory setting: +150% only briefly available) P161 = Max. regenerative current (in % of P075 rated current of rectifier/regenerating unit (factory setting: -150% only briefly available) Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 90 - Switch on: Press the I key on the PMU - Forming of the DC link takes place - Following the forming process, the status display is activated. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 91 SIMOVERT Master Drive FC the dynamic behavior of the closed-loop control of the DC link voltage can be improved. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 92: Simple Application Examples For Connecting Process Data With Connection Assignment

    P575.1 = 1004 P575.2 = 1004 (always activ) -X101/12 BE4 P590 = 1005 Basic/reserve -X101/13 BE5 -X102/15 AAM Actual Ud value P655 = 37 -X102/14 AA 4-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 93: Start-Up Aids

    Conversely, a rectifier/regenerating unit that is in the "R" state will enter the "Ready" ("B") state if the terminal is at logic L potential. 4-11 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 94 Constant value = 1 = always op. enable. Reserve set.: Constant value = 1 = via serial interface SST1 of the CUR 4-12 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 95: Overview Of The Control Word (Control Word 1 And Control Word 2)

    Can only connected at the converter P591 term. strip or SCB 1) This bit has a different meaning for the rectifier/regenerating unit as for the converter 4-13 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 96: Selecting The Source For Control Word 1 (Bit 0-7)

    1) Value 1010 cannot be set, but reset is always possible from PMU. Factory setting: xG: for basic setting with P077=0 xR: for reserve setting with P077=0 4-14 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 97: Selecting The Source For Control Word 1 (Bit 8-15)

    Value can be assigned for the selection parameters Factory setting: xG: for basic setting with P077=0 xR: for reserve setting with P077=0 4-15 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 98: Selecting The Source For Control Word 2 (Bit 16-23)

    Value can be assigned for the selection parameters Factory setting: xG: for basic setting with P077=0 xR: for reserve setting with P077=0 4-16 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 99: Selecting The Source For Control Word 2 (Bit 24-31)

    Value can be assigned for the selection parameters Factory setting: X: for P590 / P591 xG: for basic setting with P077=0 xR: for reserve setting with P077=0 4-17 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 100: Significance Of Control Word (1 And 2) Commands

    The OFF2 command is simultaneously effective from three sources (P555, P556 and P557)!! NOTE Priority of the OFF commands OFF2 > OFF1 4-18 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 101 ON status (009). After the command has been accepted ♦ an ON command is automatically executed (description, refer to control word bit 0). 4-19 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 102 ♦ The L signal of the Ud reduction command causes the "Ud reduced" message (status word 1, bit 13) to be held low (regardless of the DC link voltage level) 4-20 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 103 Bit 19: Reserve data set RDS bit 1 (MSB) command In conjunction with bit 18 "RDS bit 0", this command permits switches over between four possible data sets (see bit 18). 4-21 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 104 After the command has been accepted: ♦ An operating status > o 010 is permitted 4-22 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 105: Status Word (Status Word 1 And Status Word 2)

    - at terminal -X104:19/20 of the CUR - at terminal of the binary output 5 of the SCI (option),which is coded as slave 2 4-23 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 106: Overview Of The Status Word (Status Word 1 And Status Word 2)

    31 Pre-charging active Pre-charging not active P631 1) The meaning of this bit is different for the rectifier/regenerating unit than for the converter 4-24 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 107 SCI 1 and 2,Slave 2, BA1 4202 4203 4204 4205 4206 4207 4208 4209 only SCI 2,Slave 2, 4210 BA10 4211 BA11 4212 BA12 4-25 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 108: Significance Of The Status Word Messages

    This message is identical to the status of the relay contact at terminals 9-4/5 with which a main contactor can be driven. 4-26 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 109 Bit 31: Signal, "Pre-charging active" (H) An H signal indicates that the DC link has been charged following a successful ON command. 4-27 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 110: Setpoints

    SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word2 6003 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word3 6004 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word4 6005 SST2 (PTP1, A2-X117:1..5) Peer-to-Peer, Word5 4-28 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 111: Actual Values

    For telegram data transfer (P680,P690,P694), it is generally necessary/practical to assign "Word 01 of the telegram (PZD)" with status word 1 (r968 or r552)! 4-29 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 112: Binary Inputs

    LOW active at the terminal strip (binary outputs) (i.e. relay drops out )! Also refer to Section 4.3.1.2 "Status word". 4-30 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 113: Analog Output

    100% = 10V The parameter value in [%] for the appropriate parameter number can be taken from the parameter list, Chapter 5! 4-31 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 114 ⎛ ⎞ 27.03 74.05 − − ⎜ ⎟ ⎝ ⎠ To be adjusted: gain: P656 = +27,03V P657 = − 19,98V offset: 4-32 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 115 Offset off1 ⎝ ⎠ ⎝ ⎠ − 0.00 0.00 To be adjusted: Gain P656 = +6,67 V offset P657 = 0,00 V 4-33 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 116: Serial Interfaces

    Instruction Manuals to the various option boards. Additional information can be taken from Sections 4.3.1.1 to 4.3.1.4 "Control word, status word, setpoints, actual values". 4-34 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 117: Function Selection (P052)

    Trg Bit Warning 1001 1001 1001 1001 The factory setting for P607.002 (responsible for the optional SCI1/2 module) is not affected by P077. 4-35 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 118 Configuration of the power section ⇓ The operating display "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) appears after the factory setting has been completed. 4-36 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 119: Initialization (Mlfb Setting) (P052 = 2)

    3AC 500-600 6SE7024-1EC85-1AA0 41,0 3AC 380-480 6SE7024-1FC85-1AA0 41,0 3AC 500-600 6SE7027-2FC85-1AA0 72,0 3AC 500-600 6SE7028-6EC85-1AA0 86,0 3AC 380-480 6SE7028-8FC85-1AA0 94,0 3AC 500-600 4-37 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 120 3AC 380-480 6SE7042-0FH85-1BA0 1950,0 3AC 500-600 6SE7042-0HH85-1BA0 1950,0 3AC 660-690 6SE7042-8EH85-1BA0 2850,0 3AC 380-480 6SE7042-8FH85-1BA0 2850,0 3AC 500-600 6SE7042-7HH85-1BA0 2660,0 3AC 660-690 4-38 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 121: Download Or Upread (P052 = 3)

    P052 = 0 Function selection Return ⇓ P key ⇓ After return, the operating display appears, "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) 4-39 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 122: Hardware Configuration (P052 = 4)

    If error/fault message F050, F070 or F080 appears: see Chapter 7 ⇓ After the selected function selection has been completed, the "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) operating display appears. 4-40 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 123: Drive Setting (P052 = 5)

    ⇓ The "Switch-on inhibit" (008) or "Ready-to-switch-on" (009) operating display appears after the selected function or selection has been completed 4-41 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 124: Siemens Ag 6Se7087-6Ak85-1Aa0

    During the forming procedure, the current limit set at P160 is not effective. ⇓ When this function has been completed, the "Ready to switch on" display (009) appears. 4-42 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 125: Circuit Identification (P052 = 21)

    You will find a detailed description of the fault messages, associated fault values and a description on the warning messages in Chapter 7 "Faults and Warnings". 4-43 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 126 Circuit identification for 12-pulse mode must be carried out in succession on the 12-pulse master and on the 12- pulse slave units (see Section 3.8.5). 4-44 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 127: Display Modified Parameters (P052 = 22)

    The rectifier/regenerating unit enters the operating status o 008 (Switch-on inhibit) or o 009 (when switching on/off with the I/O keys of the PMU). On power recovery, a new ON command must be 4-45 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 128 It then switches to operating state o 010 and behaves according to the setting in P366 after the DC link voltage has dropped below the threshold P074 * 1.35 * P071. 4-46 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 129: Externally Requested And Current-Dependent U D Reduction

    DC link voltage to the specified value before recovery is started. The current-dependent U d reduction functions therefore only if an appropriate load cycle exists ! 4-47 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 130: Function Diagrams

    P787 and r786 on the PMU by parameterizing the number of the connector to be displayed at parameter r786 at P787. 4-48 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 131 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Start-Up Figure 4.4.1 Ud control, Id setpoint generation 4-49 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 132 AoteWell Automation Sales Team Sales@aotewell.com Start-Up 09.02 Figure 4.4.2 Id control, firing pulse 4-50 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 133 AoteWell Automation Sales Team Sales@aotewell.com 09.02 Start-Up Figure 4.4.3 Analog output CUR 4-51 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 134 AoteWell Automation Sales Team Sales@aotewell.com Start-Up 09.02 Figure 4.4.4 Selecting the data sets 4-52 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 135: Starting Up Optional Supplementary Boards

    If a technology board is mounted in location 2, then only one communication board (CBC, CBD, CBP2, SCB1, SCB2) may be installed in slot G. Other boards are not supported 4-53 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 136: Sequence Of Operations For Starting Up Profibus Board (Cbp2)

    The contents of the data frames transferred via these channels are identical to the structure of the parameter section (PKW) as defined by the USS specification. 4-54 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 137 Parameter data allow all parameters of the drive to be accessed, allowing parameter values, diagnostic quantities, fault messages, etc. to be called by a higher-level system without impairing the performance of the PZD transmission. 4-55 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 138: Mechanisms For Processing Parameters Via The Profibus

    Index value 255 (request applies to all index values) is meaningful only for acyclical transmission via MSAC_C1. The maximum data block length is 206 bytes with this transmission mode. 4-56 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 139: Diagnostic Tools

    SIMOVERT/SIMOREG/SIMADYN CBP File: siem8045.gsd The communication boards can only be operated on a non-Siemens master as a DP standard slave, the corresponding GSD file containing all necessary information for this mode. Detailed information about communication via PROFIBUS can be found in Section 8.2 of the compendium for SIMOVERT MASTER DRIVES Motion Control (order no.
  • Page 140 L byte: No. bytes for special diagnosis H byte: Reserved L byte: Mirroring of slot identifier 2 H byte: Mirroring of slot identifier 3 4-58 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 141 800 ms. Fault F082 Failure of PZD telegrams or a fault in the transmission channel. 4-59 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 142 SIMOVERT 6SE70 may be interrupted depending on the setting of P700 (with secondary fault F082). 4-60 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 143: Sequence Of Operations For Starting Up Can Bus Boards (Cbc)

    The figure below shows a diagram of the CAN architecture model that is oriented toward the ISO-OSI-7 layer reference model. The CBC supports the functionalities provided by layers 2 and 7 of this model. 4-61 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 144: Description Of Cbc With Can Layer 2

    This settings assigns identifier 100 to the first 4 receive PZDs, P697 = 96 identifier 101 to the second 4 receive PZDs, etc. 4-62 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 145 Identifier Data field 64 00 7F 9C 00 20 7B 00 00 00 PZD1 PZD2 PZD3 PZD4 4-63 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 146 P918 = 1 This setting assigns identifier 300 to the parameter job (request) P696 = 298 and identifier 301 to the parameter response. 4-64 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 147 SIMOVERT 6SE70 does not use double word parameters itself, these jobs can only be executed where access is available to technology board parameters (e.g. T400). 4-65 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 148: Diagnostic Tools

    Overlap between CAN identifier PZD Transmit and PZD Receive Internode Overlap between CAN identifier PZD Receive-Broadcast and PZD Receive-Multicast Overlap between CAN identifier PZD Receive-Broadcast and PZD Receive-Internode 4-66 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 149 800 ms. Fault F082 Failure of PZD telegrams or a fault in the transmission channel. 4-67 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 150 F082 with fault value 10 may be activated as a function of the telegram failure time set in P695. No fault message is generated for PKW data. 4-68 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 151: Sequence Of Operations For Starting Up The Serial I/O Board Scb1

    - P090 or P091 for logging the board - The display parameter r730 (diagnostic information) assists in the correction of problems during start- 4-69 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 152: Scb1 As Master For Sci1 And Sci2

    - as Master of SCI1 and SCI2 slaves ( S erial C ommunication I nterface). - for communication via the peer-to-peer interface. In both cases, communication between the boards takes place via fiber optic cables (recommended: Siemens plastic fiber optic cable, CA-1V2YP980/1000,200A or Siemens fiber optic cable with glass core, CLY-1V01S200/230,10A) 4.5.4.1...
  • Page 153: Scb1 As Peer-To-Peer Interface

    Details about fault or alarm messages which may occur in relation to SCB1 or SCI (F070 to F079 and A049 to A053) can be found in Section 7. 4-71 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 154: Sequence Of Operations For Starting Up The Scb2 Board

    S1 in order to prevent transmission faults. The peer-to-peer protocol allows data to be forwarded quickly from unit to unit (e.g. for implementing a setpoint cascade). 4-72 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 155: Structure Of Request/Response Telegrams

    P xxx, r xxx 0 - 999 0 - 999 Technology board H xxx, d xxx 1000 - 1999 1000 - 1999 4-73 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 156 Parameter number currently deactivated Channel not wide enough PKW number incorrect Applies only to serial interfaces Illegal parameter value Applies to BiCo selection parameters 4-74 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 157 The parameter value PWE is treated like a double word (PWE1 and PWE2). The high word is set to 0 when a single word is transferred. Parameter identifier Index Parameter value Trailer Header PWE1 PWE2 4-75 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 158 AoteWell Automation Sales Team Sales@aotewell.com Start-Up 09.02 4-76 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 159: Parameter List

    680 - 719 Communications 720 - 759 Diagnostics 760 - 779 Modulator 780 - 799 Factory Parameters 900 - 999 Profile Parameters (Profibus) Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 160 9) A factory setting value in brackets means that the specified value only applies for P077=0. See Section 4.3.9.1 "Generate factory setting" for more details. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 161: Operation Display

    The option module electronics are initialized The basic unit electronics are initialized o 001 Establish factory setting o 000 Set MLFB ∧ 1 PNU=00Hex; Type=O2; Scaling: 1Hex Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 162: General Observation Parameters

    Display of the system voltage at the regenerative bridge (average value of the three phases) ∧ 0.1 V PNU=1FHex; Type=O2; Scaling: 1Hex ∧ 0 to 1638.4V 0 - 100% Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 163 Display of terminal X102-14 (analog output) ∧ 0.1, ± 100% ∧ ± 10V at terminal PNU=27Hex; Type=O2; Scaling: 1Hex X102-14 PZD gr.: 1 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 164: General Parameters

    PMU. To exit this function the parameter must be reset to 0 (Return). ∧ 1 PNU=34Hex; Type=O2; Scaling: 1Hex Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 165 P055 is not stored in the EEPROM, and has the value "012" when the electronic power supply is switched on. ∧ 1 PNU=37Hex; Type=L2; Scaling: 1Hex Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 166: Drive Data

    DC link capacitance for the load current calculation take the above correction factor into account. ∧ 1 PNU=4CHex; Type=L2; Scaling: 1Hex Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 167 Module in slot 1 (left) in the electronics box. 4 = Module CUR (Designation: RRU=Rectifying Regenerative Unit) ∧ 1 PNU=59Hex; Type=02; Scaling: 1Hex Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 168: Hardware Configuration

    PCB in position 3 (center) of the electronic box Text as for P090 Description see P090(PCB position 2) ∧ 1 PNU=5BHex; Type=O2; Scaling: 1Hex 5-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 169: Data Of The Dc Link

    Capacitance of the DC link This parameter is automatically set when circuit identification takes place (P052=21) RDS parameter ∧ 0.01 PNU=72Hex; Type=O2; Scaling: 1Hex 5-11 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 170: Control

    Proportional gain of the DC link voltage controller This parameter is automatically set when circuit identification takes place (P052=21) RDS parameter ∧ 0.01 PNU=139Hex; Type=O2; Scaling: 1Hex 5-12 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 171 1.35 * U line,feed when current-dependent U d reduction is released (P323=1). RDS parameter ∧ 0.01 PNU=142Hex; Type=O2; Scaling: 1Hex 5-13 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 172 With the command OFF1 and current-dependent Ud reduction, P330 is active in all cases. RDS parameter ∧ 1 PNU=14AHex; Type=O2; Scaling: 1Hex 5-14 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 173: Convenience Functions

    Note: The ground fault test is only carried out if the DC link voltage is less than 50% of 1.35 P071; otherwise it is automatically skipped! ∧ 1 PNU=162Hex; Type=O2; Scaling: 1Hex 5-15 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 174 ∧ 0.1 PNU=199Hex; Type=O2; Scaling: 1Hex 5-16 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 175: Setpoint Channel

    (status word 1 bit 8 (r552)) is generated after this minimum time has elapsed RDS parameter ∧ 0.01 PNU=206Hex; Type=O2; Scaling: 1Hex 5-17 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 176: Control And Status Word

    Other values: see allowed settings in Section 4.3.1.1 (process data wiring of the control word) B/R Parameter ∧ 1 PNU=22BHex; Type=L2; Scaling: 1Hex 5-18 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 177 Other values: see allowed settings in Section 4.3.1.1 (process data wiring of the control word) B/R-Parameter ∧ 1 PNU=238Hex; Type=L2; Scaling: 1Hex 5-19 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 178 If a rectifier unit is present, this parameter is visible with effect from software version * 4.4. B/R parameter ∧ 1 PNU=23EHex; Type=L2; Scaling: 1Hex 5-20 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 179 Other values: see allowed settings in Section 4.3.1.1 (process data wiring of the control word) B/R parameter ∧ 1 PNU=24AHex; Type=L2; Scaling: 1Hex 5-21 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 180 If the function is active, pulses are released as soon as the message is available. No base / reserve settings possible ∧ 1 PNU=24FHex; Type=L2; Scaling: 1Hex 5-22 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 181 For issuing the message via a terminal the active status (bit has H-level) is inverted (broken wire proof). Parameter values, indices: as P600 ∧ 1 PNU=25EHex; Type=L2; Scaling: 1Hex 5-23 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 182 Destination wiring for the status bit "Regenerative/motoring mode" (status word 1, bit 14) Parameter values, Indices: as P600 ∧ 1 PNU=266Hex; Type=L2; Scaling: 1Hex 5-24 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 183 For issuing the message via a terminal the active status (bit has H-level) is inverted (broken wire proof). Parameter values, Indices: as for P600 ∧ 1 PNU=26FHex; Type=L2; Scaling: 1Hex 5-25 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 184 For issuing the message via a terminal the active status (bit has H-level) is inverted (broken wire proof). Parameter values, indices: as P600 ∧ 1 PNU=277Hex; Type=L2; Scaling: 1Hex 5-26 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 185: Analog Input/Output

    Slave 2, analog input 3 Condition: The related SCB board must be reported via P090 and P091, respectively ∧ 1 PNU=294Hex; Type=O2; Scaling: 1Hex 5-27 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 186 Slave 2, analog output 1 i005: Sl22 Slave 2, analog output 2 i006: Sl23 Slave 2, analog output 3 ∧ 0.01 V PNU=29AHex; Type=I2; Scaling: 1Hex 5-28 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 187: Communications

    = SST1: bus address of serial comm. interface 1 (CUR) i002 = SCB: SCB baud rate, if P682=1, 2 ∧ 1 PNU=2ABHex; Type=O2; Scaling: 1Hex 5-29 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 188 2 (CUR with PTP1 option), if Peer-to-Peer protocol is selected (P688=1), from 1 to 5 net data words can be sent. ∧ 1 PNU=2AEHex; Type=O2; Scaling: 1Hex 5-30 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 189 Word 02 of the (process data part of the) telegram i016 Word16 of the (process data part of the) telegram ∧ 1 PNU=2B2Hex; Type=O2; Scaling: 1Hex 5-31 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 190 0 to 65535 3/ HBR P701 CB Parameter 6 3/ H Communication board parameter 6 See P696 ∧ 1 PNU=2BDHex; Type=O2; Scaling: 1Hex 5-32 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 191 PNU=2C1Hex; Type=O2; Scaling: 1Hex 3/ HBR P706 CB Parameter 11 3/ H Communication board parameter 11 See P696 ∧ 1 PNU=2C2Hex; Type=L2; Scaling: 1Hex 5-33 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 192: Diagnostics

    Headroom of the CPU on the CUR module. ∧ 1 % PNU=2D5Hex; Type=O2; Scaling: 1Hex PZD gr.: 1 ∧ 100% computer time free Analog output: 100% 5-34 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 193 Trip description by: r947 Fault number r949 Fault value r951 List of fault texts P952 Number of faults ∧ 1 PNU=2ECHex; Type=O2; Scaling: 1Hex 5-35 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 194: Modulator

    < pulsating threshold, the control angle is limited to 165°, for currents > (pulsating threshold+P777) to P776 with linear interpolation inbetween) RDS parameter ∧ 1 % PNU=309Hex; Type=O2; Scaling: 1Hex 5-36 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 195: Factory Parameters

    PNU=319Hex; Type=O2; Scaling: 1Hex 0 to 65535 3/U BR P799 Special Access Parameter for special access ∧ 1 PNU=31FHex; Type=O2; Scaling: 1Hex 5-37 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 196: Profile Parameters

    Source of the switching command 'base / reserve settings' (control word 2, bit 30) This parameter performs the same function as P590. For description, see P590. ∧ 1 PNU=3A0Hex; Type=L2; Scaling: 1Hex 5-38 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 197 List of fault texts; every fault text is saved in the index equivalent to its fault number. ∧ 1 PNU=3B7Hex; Type=O2; Scaling: 1Hex 5-39 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 198 If a warning (numbers 65 to 80) is active, the related segment in the display is ON ∧ 1 PNU=3BDHex; Type=V2; Scaling: 1Hex 5-40 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 199 It takes about 15s to process all of the values. During this time, the PMU stays in the Values mode. ∧ 1 PNU=3CBHex; Type=O2; Scaling: 1Hex 5-41 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 200 PNU=3DFHex; Type=O2; Scaling: 1Hex r992 PNU-Lst.3 chnged List of the changed parameter numbers; part 3 See r990 ∧ 1 PNU=3E0Hex; Type=O2; Scaling: 1Hex 5-42 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 201: Operator Control

    Table 6.1 Function of the operator control elements on the PMU Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 202: Displays 8.8.8.8

    "window" can be moved to view the parameter value. By pressing <P> again, it is possible to switch back to the parameter number level.. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 203: Structure

    Parameter indexed? Index level highest index Parameter value level highest value Return to parameter number Figure 6.2 Operator control structure using the PMU Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 204 Handling of fault and alarm messages (reset, move into the "background" in order to parameterize) is described in Chapter 7 in detail. Figure 6.4 Shifting the PMU display for parameters values with more than 4 digits Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 205: Fault And Alarm Messages

    The unit will not start up unless this message is acknowledged (except if auto restart has been selected; see under P366 and Section 4.3.10.1). Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 206 The interval between two identical line voltage zeros of the voltage for the regenerating converter must not be greater than 450 deg.. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 207 A check is make to see whether the phase sequence of the rectifier bridge is the same as that of the regenerative bridge. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 208 Non-permissible microprocessor status contactors without RC elements, unshielded cables, faulty The microprocessor is monitored by shielding connections ...) internal hardware for non-permissible states Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 209 Following receipt of a valid telegram, no further telegrams were received for longer than the time set with parameter P687.i001 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 210 TB TB/CB heartbeat error and/or CB - Hardware fault (replace TB and/or TB or CB has stopped processing the heartbeat counter. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 211 (P052=21) The abort took place because the "Inhibit regenerating" command was given during circuit identification (see control word 1, bit 12 and P572) Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 212 (gate X15 or X25) Thyristor cannot block (gate X16 or X26) F116 Fault on the intelligent I/O module See User's Manual of the TB module F150 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 213: Alarm Messages

    See also under fault F022 and parameter P785. The permissible I t value is reached at the maximum permissible load cycle (see Section 14, Figure 14.1) Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 214 See user's manual for the TB module 0...15 A113.. r960 TB Warning 17...32 A128 ⎯⎯ See user's manual for the TB module 0...15 7-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 215: Maintenance

    T = 40 °C. To guarantee the availability of the unit at all times, the fans must be replaced in good time. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 216: Replacing Components

    The air must be discharged from the unit in the upward direction. Fan E1 Figure 8.2 Fan (AC 230V) for size E Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 217 The fan box weighs approx. 16 kg for size H, and approx. 32 kg for size K. This must be taken into account when removing the fan box. Non-observance of warning notices can result in severe personal injury or considerable property damage. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 218: Replacing Modules

    / removal aids. Figure 8.5 Electronics box, equipped with CUR (slot 1) and options (slots 2 and 3) Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 219 The earth connection must be restored by tightening the screws marked with an earthing sign on the electronics box (size H) or on the electronics slide-in unit (size K). Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 220 This is best done by touching a conductive earthed object (e.g. a bare metal part of the control cabinet) directly beforehand. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 221: Replacing Thyristor Modules With Sizes C And E

    Also use original-length screws when screwing the thyristor modules to the busbars. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 222: Power Interface Module Spare Parts

    Dimensioning of the load resistors: I dav [A] R75 R76 R77 R78 R79 R80 [Ω] [Ω] [Ω] Rating plate Voltage class 480V 1300 1023 1333 1780 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 223 A1681 . R ≥ 47Ω 0.10% for The load resistance setpoint refers to the DC link current I stated on the rating plate. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 224 7 A T 2 5 0 V C98043-A1682 R 7 7 R 7 9 R 7 5 R 7 8 R 8 0 R 7 6 8-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 225 7 A T 2 5 0 V 7 A T 2 5 0 V C98043-A1685 R 7 9 R 7 7 R 7 5 8-11 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 226: Replacing Thyristor Blocks

    Loosen M6 nut and pull the thyristor block out upwards at an angle. The thyristor blocks are installed in the reverse order. 8-12 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 227: Disassembling The Thyristor Blocks For Size K

    , swing the thyristor block out forwards and pull the thyristor block out upwards at an angle. The thyristor blocks are installed in the reverse order. 8-13 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 228 AoteWell Automation Sales Team Sales@aotewell.com Maintenance 09.02 8-14 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 229: Options

    SC60, terminal block SE300 and hardware operating instructions T400 Technology board (incl. short description) 6DD1606-0AD0 Hardware and configuring manual 6DD1903-0EA0 Table 9.1 Option boards and bus adapter Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 230 Optional supplementary boards can be installed only in conjunction with the LBA option. If an LBA is not already fitted in the SIMOVERT 6SE70, one must be installed in the electronics box to accommodate the optional board. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 231: Interface Boards

    Serial I/O board (only in conjunction with SCB1) Board 6SE7090-0XX84-3EF0 description 6SE7080-0CX84-0BC0 Binary inputs and outputs for coupling to the SCB1 via fiber-optic cable. Table 9.4 Interface boards Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 232: Power Supply

    Displayed number Number to be entered on the OP1S Basic device rxxx, Pxxx (0)xxx parameter Parameter of a Hxxx, dxxx 1xxx technology module Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 233 The predecessor of the OP1S (the OP1) cannot be used with software version V4.0 and higher because of its differing coupling mechanisms! The OP1S, however, is a suitable replacement for the OP1 if used with older device software. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 234: Mechanical Design

    3.0 or higher (see the label on the EPROM, fourth number block must be 30 or higher: V98113-A1800-A001-30, V98113-A1800-A001-31, ... The software version can also be read from parameter r720.01. The contents must be 3.0 or greater). Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 235: Installation

    Number of net data words for peer-to-peer link P687.i003 Telegram failure time P688 Selection of the protocol Parameterization for "12-pulse mode" see Section 3.8.3. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 236: Drivemonitor

    PMU-X300 (9-way SUB D connector, RS485-/RS232 interface). It is only possible to operate one of the two possible connections (X100 or X300)! Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 237: Creating An Online Link To The Rectifier/Regenerating Unit

    To switch to online mode, select View - Online or the appropriate button on the toolbar. If the message "Device is not networked" then appears, then "Offline mode" is currently selected. You can switch to online mode under File - Drive Settings. Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 238: Further Information

    SIMOVERT 6SE70 Order No.: 6SW1700-5JC00-1AA0 NOTICE DriveMonitor will run under Windows 95/98/Me or Windows NT4 / Windows 2000, but not under Windows 3.x. 9-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 239 PCB- Power Interface 6SE7041-8EK85-1MA0 6SE7041-3EK85-1AD0 6SE7041-8EK85-1AD0 PCB- Power Interface 6SE7041-8HK85-1MA0 6SE7041-3FK85-1AD0 6SE7041-5FK85-1AD0 6SE7041-8FK85-1AD0 6SE7041-3HK85-1AD0 6SE7041-5HK85-1AD0 6SE7041-8HK85-1AD0 Parameterization unit 6SE7090-0XX84-2FA0 all unit types - 1AA0 10-1 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 240 6SE7028-6EC85-1AA0 V21 to V26 Thyristor module 6SY7010-0AA17 6SE7033-1EE85-1AA0 V21 to V26 Thyristor module 6SY7010-0AA07 6SE7031-7EE85-1AA0 V21 to V26 Thyristor module 6SY7010-0AA20 6SE7033-8EE85-1AA0 10-2 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 241 6SE7041-0HH85-1AA0 Ebene B Thyristor block with snubber RC network 6SY7010-0AB30 6SE7041-0HH85-1AA0 Ebene A Thyristor block with snubber RC network 6SY7010-0AB31 6SE7041-3HK85-1AA0 6SE7041-3HK85-1AD0 10-3 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 242 6SE7038-2EH85-1AA0 6SE7041-0EH85-1AA0 6SE7037-7FH85-1AA0 6SE7041-0FH85-1AA0 6SE7037-7HH85-1AA0 6SE7041-0HH85-1AA0 6SE7041-3EK85-1AA0 6SE7041-3EK85-1AD0 6SE7041-8EK85-1AA0 6SE7041-8EK85-1AD0 6SE7041-3FK85-1AA0 6SE7041-3FK85-1AD0 6SE7041-5FK85-1AA0 6SE7041-5FK85-1AD0 6SE7041-8FK85-1AA0 6SE7041-8FK85-1AD0 6SE7041-3HK85-1AA0 6SE7041-3HK85-1AD0 6SE7041-5HK85-1AA0 6SE7041-5HK85-1AD0 6SE7041-8HK85-1AA0 6SE7041-8HK85-1AD0 10-4 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 243 6SE7034-2HE85-1AA0 Fuse link 6SY7010-2AA12 6SE7036-1EE85-1AA0 Fuse link 6SY7010-2AA13 6SE7022-7FC85-1AA0 Fuse link 6SY7010-2AA14 6SE7027-2FC85-1AA0 Fuse link 6SY7010-2AA15 6SE7028-8FC85-1AA0 Fuse link 6SY7010-2AA16 6SE7031-5FE85-1AA0 6SE7031-4HE85-1AA0 10-5 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 244 6SE7028-1EC85-1AA0 6SE7022-7FC85-1AA0 6SE7024-1FC85-1AA0 6SE7027-2FC85-1AA0 6SE7028-8FC85-1AA0 6SE7031-7EE85-1AA0 6SE7032-2EE85-1AA0 6SE7033-1EE85-1AA0 6SE7033-8EE85-1AA0 6SE7034-6EE85-1AA0 6SE7036-1EE85-1AA0 6SE7031-5FE85-1AA0 6SE7032-4FE85-1AA0 6SE7032-7FE85-1AA0 6SE7033-5FE85-1AA0 6SE7034-2FE85-1AA0 6SE7035-4FE85-1AA0 6SE7031-4HE85-1AA0 6SE7032-2HE85-1AA0 6SE7032-7HE85-1AA0 6SE7034-2HE85-1AA0 6SE7035-3HE85-1AA0 10-6 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 245 6SE7033-1EE85-1AA0 6SE7033-8EE85-1AA0 6SE7034-6EE85-1AA0 6SE7036-1EE85-1AA0 6SE7031-5FE85-1AA0 6SE7032-4FE85-1AA0 6SE7032-7FE85-1AA0 6SE7033-5FE85-1AA0 6SE7034-2FE85-1AA0 6SE7035-4FE85-1AA0 6SE7031-4HE85-1AA0 6SE7032-2HE85-1AA0 6SE7032-7HE85-1AA0 6SE7034-2HE85-1AA0 6SE7035-3HE85-1AA0 6SY7010-7AA02 6SE7038-2EH85-1AA0 6SE7041-0EH85-1AA0 6SE7037-7FH85-1AA0 6SE7041-0FH85-1AA0 6SE7037-7HH85-1AA0 6SE7041-0HH85-1AA0 10-7 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 246 6SE7031-5FE85-1AA0 6SE7032-4FE85-1AA0 6SE7032-7FE85-1AA0 6SE7033-5FE85-1AA0 6SE7034-2FE85-1AA0 6SE7035-4FE85-1AA0 6SE7031-4HE85-1AA0 6SE7032-2HE85-1AA0 6SE7032-7HE85-1AA0 6SE7034-2HE85-1AA0 6SE7035-3HE85-1AA0 T1, T2 Current transformer 6SY7010-5AA03 6SE7038-2EH85-1AA0 6SE7041-0EH85-1AA0 6SE7037-7FH85-1AA0 6SE7041-0FH85-1AA0 6SE7037-7HH85-1AA0 6SE7041-0HH85-1AA0 10-8 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 247 T1, T2 Current transformer 6SY7010-5AA04 6SE7041-3EK85-1AA0 6SE7041-3EK85-1AD0 6SE7041-8EK85-1AA0 6SE7041-8EK85-1AD0 6SE7041-3FK85-1AA0 6SE7041-3FK85-1AD0 6SE7041-5FK85-1AA0 6SE7041-5FK85-1AD0 6SE7041-8FK85-1AA0 6SE7041-8FK85-1AD0 6SE7041-3HK85-1AA0 6SE7041-3HK85-1AD0 6SE7041-5HK85-1AA0 6SE7041-5HK85-1AD0 6SE7041-8HK85-1AA0 6SE7041-8HK85-1AD0 10-9 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 248 AoteWell Automation Sales Team Sales@aotewell.com Spare-parts 09.02 10-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 249 P142 Inverter Resist. i001=0.000 i001= i001= i002=0.000 i002= i002= i003=0.000 i003= i003= i004=0.000 i004= i004= 12-1 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 250 P318 DC V(set,red) i001=80.00 i001= i001= i002=80.00 i002= i002= i003=80.00 i003= i003= i004=80.00 i004= i004= 12-2 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 251 P518 Deviation Time i001=0.10 i001= i001= i002=0.10 i002= i002= i003=0.10 i003= i003= i004=0.10 i004= i004= P554 Src ON/OFF1 i001=1010 i001= i001= i002=1001 i002= i002= 12-3 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 252 P589 Src No Ext Warn2 i001=1 i001= i001= i002=1 i002= i002= P590 Src Base/Reserve 1005 P591 Src ContactorMsg 12-4 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 253 P631 Trg Bit Charging i001=0 i001= i001= i002=0 i002= i002= P655 CUR AnaOutActVal P656 CUR AnaOutGain 10.00 12-5 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 254 P666 SCI AnaOutOffs i001=0.00 i001= i001= i002=0.00 i002= i002= i003=0.00 i003= i003= i004=0.00 i004= i004= i005=0.00 i005= i005= i006=0.00 i006= i006= 12-6 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 255 P688 SST2 Protocol P689 SCB Peer2PeerExt i001=0 i001= i001= i002=0 i002= i002= i003=0 i003= i003= i004=0 i004= i004= i005=0 i005= i005= 12-7 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 256 P700 CB Parameter 5 P701 CB Parameter 6 P702 CB Parameter 7 P703 CB Parameter 8 P704 CB Parameter 9 P705 CB Parameter 10 12-8 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 257 P917 Change Reports P918 CB Bus Address P927 Parameter Access P928 Src Base/Reserve 1005 P952 # of Faults P970 Factory Settings P971 EEPROM Storing 12-9 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 258 AoteWell Automation Sales Team Sales@aotewell.com Logbook 05.00 Date/time Name/department Fault and diagnostic Measures messages 12-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 259 The PC boards can be disposed of thermally. The number of components containing hazardous substances is only slight. The recyclable plastic parts are designated in accordance with DIN 54840 and marked with the recycling symbol. 13-1 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 260 AoteWell Automation Sales Team Sales@aotewell.com Environmental Compatibility 09.02 13-2 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 261: Technical Data

    Sales@aotewell.com 09.02 Technical Data Technical Data In the event of conditions of use other than those listed in this chapter, please contact your local Siemens branch or national subsidiary. Coolant temperature 0 °C to +40 °C − 25 °C to +70 °C Storage temperature −...
  • Page 262 Cooling air requirement 0,028 0,028 0,028 Sound pressure level, dimensions, weight Sound pressure level dB(A) Size Width Height (without securing bracket) Depth Weight app. 14-2 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 263 Sound pressure level dB(A) Size Width Height 1050 1050 1050 1050 1050 1050 Depth Standard Option Weight app. 43.5 51.5 51.5 14-3 Siemens AG 6SE7087 6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 264 The permissible output current in parallel mode is reduced (due to current division between the power sections) by 10 % as compared to the sum of the rated currents of the separate power sections. 14-4 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 265 0,028 0,028 0,028 Sound pressure level, dimensions, weight Sound pressure level dB(A) Size Width Height (without securing bracket) Depth Weight app. 14-5 Siemens AG 6SE7087 6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 266 Sound pressure level dB(A) Size Width Height 1050 1050 1050 1050 1050 1050 Depth Standard Option Weight app. 43.5 44.5 44.5 53.5 53.5 14-6 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 267 The permissible output current in parallel mode is reduced (due to current division between the power sections) by 10 % as compared to the sum of the rated currents of the separate power sections. 14-7 Siemens AG 6SE7087 6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 268 Sound pressure level, dimensions, weight Sound pressure level dB(A) Size Width Height 1050 1050 1050 1050 1050 Depth Standard Option Weight app. 44.5 53.5 53.5 14-8 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 269 The permissible output current in parallel mode is reduced (due to current division between the power sections) by 10 % as compared to the sum of the rated currents of the separate power sections. 14-9 Siemens AG 6SE7087 6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 270: Power Reduction At Increased Coolant Temperature

    Figure 14.3 Maximum values for rated current and rated voltage depending on installation altitude 14-10 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 271: Applied Standards

    Electrical fast transient / burst requirements EN 60146-1-1: 1993 Semiconductor converters; General requirements and line-commutated converters: Part 1-1 Definition of basic requirements (IEC146-1-1991) 14-11 Siemens AG 6SE7087 6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 272 Technical Data 09.02 Sources DIN standards and foreign standards: Beuth-Verlag GmbH Burggrafenstraße 6 10787 Berlin DIN VDE regulations: VDE-Auslieferungsstelle Merianstraße 29 63069 Offenbach 14-12 Siemens AG 6SE7087-6AK85-1AA0 Rectifier/Regenerating Unit Operating Instructions AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 273 The DriveMonitor software tool is provided for commissioning, parameterizing and diagnosing the common rectifier via a PC. DriveMonitor is supplied on the same CD-ROM (order number: 6SX7010-0FA10) as the operating instructions for the 6SE70 converter used in conjunction with the rectifier unit. AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...
  • Page 274 Environmental compatibility 09.02 Technical data 09.02 Siemens AG Elektronikwerk Wien © Siemens AG, 1994 Postfach 83, A-1211 Wien Subject to change without notice Order No.: 6SE7087-6AK85-1AA0 Siemens Aktiengesellschaft Printed in Austria AoteWell LTD Buy Siemens PLC HMI Drives at AoteWell.com https://www.aotewell.com...