Starting up the FM 453
Speed Assignment
This test is only necessary in the case of servo drives (MD61 = 0).
of the Drive
Use the following flow chart to check that the speed assignment of the drive
corresponds to the parameterization in the machine data.
If you have carried out the "Check encoder actuation" startup step correctly,
with each traverse, the actual traversing velocity of the machine axis will be
shown on the "Velocity" display.
This test has to be conducted in order to ensure that the parameterized
K
Fine calibration is then possible in the "Optimize position control" startup
step with the aid of the K
Select
Mode = Control
Voltage level 2
Set
Voltage level 1 = 0
Voltage level 2 = 0.1
Set
Servo = ON
Start axis
Plus or minus direction
(be sure there is enough room!)
Read actual velocity during the
Is actual speed = 0.1 MD23
Yes
Fig. 7-13 Testing Speed Assignment
7-26
factor is implemented with the correct value in the position control circuit.
v
factor checkback signal in the service data.
v
U
U
max
traverse
correct?
No
MD23 correct?
No
Parameterization
MD23 – Maximum speed
Set
Activate machine data
END
= MD43
max
Yes
Correct RPM allocation accord-
ingly on the drive
FM 453 Servo Drive / Step Drive Positioning Module
C79000-G7076-C453-01