H2: Multi-Function Digital Outputs - YASKAWA L1000A Technical Manual

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

5.7 H: Terminal Functions

◆ H2: Multi-Function Digital Outputs

H2-01 to H2-05: Terminals M1-M2, M3-M4, M5-M6, P1-C1, and P2-C2 Function Selection
The drive has five multi-function output terminals.
through H2-05.
No.
H2-01
H2-02
H2-03
H2-04
H2-05
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-set Speed Agree 1
4
Speed Detection 1
5
Speed Detection 2
6
Drive Ready (READY)
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Speed Reference Source
A
Up/Down Command Source
B
Torque Detection 1
E
Fault
F
Not used (Through Mode)
10
Minor Fault
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-set Speed Agree 2
15
Speed Detection 3
16
Speed Detection 4
18
Torque Detection 2
1A
During Reverse
<1> Available in drive software PRG: 7017 or later.
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
An Up/Down command is input or the drive is during deceleration or during DC injection.
Setting 1: Zero Speed
Terminal closes whenever the output speed or motor speed (CLV, CLV/PM) becomes less than the minimum output speed
set to E1-09 or S1-01.
Status
Open
The operating speed is greater than the minimum output frequency (E1-09) or the zero speed level at stop (S1-01).
Closed
The operating speed is less than or equal to the minimum output frequency (E1-09) or the zero speed level at stop (S1-01).
Note: When using CLV or CLV/PM control modes, the output terminal will close when the motor speed becomes less than or equal to
the zero speed level set for S1-01. In all other control modes, the output terminal will close when the output frequency becomes
less than or equal to the minimum output frequency set for E1-09.
208
Parameter Name
Terminals M1-M2 Function Selection
Terminals M3-M4 Function Selection
Terminals M5-M6 Function Selection
Terminals P1-C1 Function Selection (photocoupler)
Terminals P2-C2 Function Selection (photocoupler)
Table 5.12 Multi-Function Digital Output Terminal Settings
Function
Page
Table 5.12
lists the functions available for these terminals using H2-01
Setting
208
1B
During Baseblock 2 (N.C.)
208
1C
Motor 2 Selection
209
1D
During Regeneration
209
1E
Restart Enabled
210
1F
Motor Overload Alarm (oL1)
210
20
Drive Overheat Pre-alarm (oH)
211
2F
Maintenance Period
211
30
During Torque Limit
211
33
Within Position Lock Bandwidth
211
37
During Frequency Output
211
50
Brake Control
211
47
Input Phase Loss
212
4E
Braking Transistor Fault (rr)
212
51
Output Contactor Control
212
52
Door Zone Reached
212
53
Not Zero Speed
212
54
Light Load Direction
212
55
Light Load Direction Detection Status
212
58
Safe Disable Status
213
5C
Motor Current Monitor
<1>
213
60
Internal Cooling Fan Alarm
211
61
Motor Pole Search Status
214
100 to 161
Functions 0 to 61 with Inverse Output
Description
Description
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Setting Range
0 to 161
50: Brake control
0 to 161
51: Output control contactor
0 to 161
6: Drive ready
0 to 161
37: During frequency output
0 to 161
F: Through Mode
Function
Default
Page
214
214
215
215
215
215
215
215
215
215
216
216
216
216
216
216
216
216
216
216
216
216
217