◆ Sinking/Sourcing Mode Selection for Safe Disable Inputs
Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe
Disable inputs H1 and H2 as shown in
Table 3.12 Safe Disable Input Sink / Source / External Power Supply Selection
Sinking Mode
Sourcing Mode
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Table 3.12
(Default: Sink mode, internal power supply).
Drive Internal Power Supply
Jumper S3
24 Vdc
HC
H1
H2
Jumper S3
24 Vdc
HC
H1
H2
3.9 Control I/O Configuration
External 24 Vdc Power Supply
Jumper S3
24 Vdc
HC
External
24 Vdc
H1
H2
Jumper S3
24 Vdc
HC
External
24 Vdc
H1
H2
3
85