C.12 Self-Diagnostics

C.12 Self-Diagnostics
The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the
self-diagnosis function, use the following procedure.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or
serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power
supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait
at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
1.
Turn on the power to the drive.
2.
Note the present terminal S6 function selection setting (H1-06) and set it for the communications test mode
(H1-06 = 67).
3.
Turn off the power to the drive.
4.
With the power off, wire the drive as shown in the following diagram, connecting terminals R+ and S+, R- and S-,
and S6 and SC.
Figure C.9
YEA_TMonly
5.
Set jumper S3 to source mode (internal power supply).
6.
Turn the power to the drive back on.
7.
Turn off the power supply.
8.
Remove the wire jumpers from terminal R+, R-, S+, S-, and S6-SC. Set back jumper S3 to its original position.
Set terminal S6 to its original function.
9.
Return to normal operation.
470
Figure C.9 Terminal Connections for Communication Self-Diagnostics
E(G) HC H1 H2 DM+ DM- IG R+ R- S+ S-
V+ AC V- A1 A2 FM AM AC P1 C1 P2 C2
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual