C.4 MEMOBUS/Modbus Setup Parameters

C.4 MEMOBUS/Modbus Setup Parameters
◆ MEMOBUS/Modbus Serial Communication
This section describes parameters necessary to set up MEMOBUS/Modbus communications.
H5-01: Drive Slave Address
Sets the drive slave address used for MEMOBUS/Modbus communications.
Note: Cycle the power after changing this parameter to enable the new setting.
No.
H5-01
<1> If the address is set to 0, no response will be provided during communications.
Each slave drive must be assigned a unique slave address for serial communications to work. Setting H5-01 to any value
besides 0 assigns the drive its address in the network. Slave addresses do not need to be assigned in sequential order, but
no two drives may share the same address.
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note: Cycle the power after changing this parameter to enable the new setting.
No.
H5-02
H5-02
0
1
2
3
4
H5-03: Communication Parity Selection
Sets the parity used for MEMOBUS/Modbus communications.
Note: Cycle the power after changing this parameter to enable the new setting.
No.
H5-03
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
448
Parameter Name
Drive Slave Address
Parameter Name
Communication Speed Selection
Communication Speed
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
Parameter Name
Communication Parity Selection
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Setting Range
0 to FFH
<1>
Setting Range
0 to 5
H5-02
Communication Speed
5
6
7
8
Setting Range
0 to 2
Default
1FH
Default
3
38400 bps
57600 bps
76800 bps
115200 bps
Default
0