No.(Addr.)
Name
H5-06
Drive Transmit Wait Time
(42AH)
H5-07
RTS Control Selection
(42BH)
H5-09
Communication Fault Detection
(435H)
Time
H5-10
Unit Selection for MEMOBUS/
(436H)
Modbus Register 0025H
H5-11
Communications ENTER Function
(43CH)
Selection
<14> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
◆ L: Protection Functions
L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,
frequency detection, fault reset, overtorque detection, torque limits, and other types of hardware protection.
■
L1: Motor Protection
No. (Addr.)
Name
L1-01
Motor Overload Protection
(480H)
Selection
L1-02
Motor Overload Protection Time
(481H)
L1-03
Motor Overheat Alarm Operation
(482H)
Selection (PTC thermistor input)
<44>
L1-04
Motor Overheat Fault Operation
(483H)
Selection (PTC thermistor input)
<44>
L1-05
Motor Temperature Input Filter
(484H)
Time (PTC thermistor input)
<44>
L1-13
Continuous Electrothermal
(46DH)
Operation Selection
<5> Default setting is determined by the control mode (A1-02).
<44> Available in drive software versions PRG: 7017 or later.
■
L2: Undervoltage Detection
No. (Addr.)
Name
L2-05
Undervoltage Detection Level
(489H)
(Uv)
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
<15> Default setting value is dependent on the setting for the input voltage (E1-01).
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Description
All Modes
Sets the wait time between receiving and sending data.
All Modes
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
All Modes
Sets the time required to detect a communications error. Adjustment may be needed when
networking several drives.
All Modes
0: 0.1 V units
1: 1 V units
All Modes
0: Drive requires an Enter command before accepting any changes to parameter settings.
1: Parameter changes are activated immediately without the Enter command.
Description
All Modes
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
5: PM motor with constant torque characteristics
All Modes
Sets the motor thermal overload protection (oL1) time.
All Modes
Sets operation when the motor temperature analog input (H3-02 or H3-10 = E) exceeds the oH3
alarm level.
0: Ramp to stop
1: Coast to stop
2: Emergency Stop (Fast Stop) (decelerate to stop using the deceleration time in C1-09)
3: Alarm only ("oH3" will flash)
All Modes
Sets stopping method when the motor temperature analog input (H3-02 or H3-10 = E) exceeds
the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Emergency Stop (Fast Stop) (decelerate to stop using the deceleration time in C1-09)
All Modes
Adjusts the filter for the motor temperature analog input (H3-02 or H3-10 = E).
All Modes
0: Disabled
1: Enabled
Description
All Modes
Sets the DC bus undervoltage trip level.
B.3 Parameter Table
Setting
Page
Default: 5 ms
common_
TMonly
Min: 5 ms
449
Max: 65 ms
common_
Default: 1
TMonly
Min: 0
449
Max: 1
common_
Default: 2.0 s
TMonly
Min: 0.0 s
450
Max: 10.0 s
common_
Default: 0
TMonly
Min: 0
450
Max: 1
common_
Default: 0
TMonly
Min: 0
450
Max: 1
Setting
Page
common_
TMonly
Default:
<5>
Min: 0
223
Max: 5
Default: 1.0 min
common_
TMonly
Min: 0.1 min
225
Max: 5.0 min
common_
TMonly
Default: 3
Min: 0
226
Max: 3
common_
TMonly
Default: 1
Min: 0
227
Max: 2
Default: 0.20 s
common_
TMonly
Min: 0.00 s
227
Max: 10.00 s
common_
Default: 1
TMonly
Min: 0
227
Max: 1
Setting
Page
Default:
<9> <15>
common_
TMonly
Min: 150 Vdc
227
Max: 210 Vdc
<9>