A.1 Three-Phase 200 V Class Drives
A.1 Three-Phase 200 V Class Drives
Item
CIMR-LU2
Maximum Applicable Motor Capacity (HP)
Input Current (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Input Power (kVA)
Rated Output Capacity (kVA)
Rated Output Current (A)
Output
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Speed (Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> DC is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency can be set up to 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be set up to 5 kHz while keeping this current rating. Higher carrier frequency settings require derating.
378
Table A.1 Power Ratings (Three-Phase 200 V Class)
0008 0011 0014 0018 0025 0033 0047 0060 0075 0085 0115 0145 0180 0215 0283 0346 0415
2
3
4
3.7 (5)
<1>
7.5
11
15.6
<2>
4.1
5.8
7.8
3
4.2
5.3
<4>
<5>
<5>
<5>
8
11
14
<5>
<5>
<5>
User adjustable between 2 and 15 kHz
Specification
7.5
10
15
20
18.9
28
37
52
68
Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc
-15 to 10%
9.5
14
18
27
36
6.7
9.5
12.6
17.9
23
<5>
<5>
<5>
<5>
<5>
17.5
25
33
47
60
<5>
<5>
<5>
<5>
<5>
150% of rated output current for 60 s
Three-phase 200 to 240 V (proportional to input voltage)
200 Hz (user-set)
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
25
30
40
50
60
80
82
111
136
164
<3>
±5%
44
37
51
62
75
29
32
44
55
69
<5>
<5>
<5>
<6>
<6>
75
85
115
145
180
<5>
<5>
<5>
<6>
<6>
User adjustable between 2 and 10 kHz
75
100
125
150
200
271
324
394
91
124
148
180
82
108
132
158
<6>
<6>
<6>
<6>
215
283
346
415
<6>
<6>
<6>
<6>