L8: Drive Protection - YASKAWA L1000A Technical Manual

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

L7-16: Torque Limit Process at Start
Assigns a time filter to allow the torque limit to build at start.
No.
L7-16
Setting 0: Disabled
Toque limit is created at start without a delay time. Disable L7-16 to maximize response time when the application
requires sudden acceleration or deceleration at start.
Setting 1: Enabled
A time filter is added to allow the torque limit to build at start.

◆ L8: Drive Protection

L8-02: Overheat Alarm Level
Sets the overheat alarm (oH) detection level.
The drive will output an alarm when the heatsink temperature exceeds the alarm level set in parameter L8-02.
When an output terminal is set for the oH pre-alarm (H2- = 20), the switch will close when the heatsink temperature
rises above L8-02.
No.
L8-02
L8-03: Overheat Pre-Alarm Operation Selection
Sets the operation when an overheat pre-alarm is detected.
No.
L8-03
Setting 0: Ramp to stop
If an overheat alarm occurs, the drive decelerates to stop using the deceleration ramp currently selected. If a digital output
is programmed for "fault" (H2- = E), this output will be triggered.
Setting 1: Coast to stop
If heatsink overheat (oH) occurs, the drive switches off the output and the motor coasts to stop. If a digital output is
programmed for "fault" (H2- = E), this output will be triggered.
Setting 2: Fast Stop
If an overheat alarm occurs, the drive decelerates to stop using the Fast Stop ramp (C1-09). If a digital output is
programmed for "fault" (H2- = E), this output will be triggered.
Setting 3: Alarm only
If an overheat alarm occurs, an alarm is output and the drive continues operation.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Parameter Name
Torque Limit Process at Start
Parameter Name
Overheat Alarm Level
Parameter Name
Overheat Pre-Alarm Operation Selection
5.8 L: Protection Functions
Setting Range
Default
0 to 1
Setting Range
Default
50 to 150°C
Determined by o2-04
Setting Range
Default
0 to 3
1
3
5
235

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents