b7-02: Droop Control Delay Time
■
Adjusts the responsiveness of Droop control. Reduce the setting if the reaction time is too long, and increase it if hunting
occurs.
No.
b7-02
◆ b8: Energy Saving
The Energy Saving function can significantly increase the efficiency of an IPM motor.
Note: The Energy Saving function should be used only with a Yaskawa IPM motor.
b8-01: Energy Saving Control Selection
■
Enables or disables the Energy Saving function.
No.
b8-01
Setting 0: Disabled
Setting 1: Enabled
■
b8-16: Energy Saving Control Constant (Ki)
Enter the Energy Saving value (Ki) as specified on the motor nameplate (for IPM motors only).
No.
b8-16
b8-17: Energy Saving Control Constant (Kt)
■
Enter the Energy Saving value (Kt) as specified on the motor nameplate (for IPM motors only).
No.
b8-17
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Parameter Name
Droop Control Delay Time
Parameter Name
Energy Saving Control Selection
Parameter Name
Energy Saving Control Constant (Ki)
Parameter Name
Energy Saving Control Constant (Kt)
5.2 b: Application
Setting Range
Default
0.03 to 2.00 s
0.05 s
Setting Range
Default
0 or 1
Setting Range
Default
0.00 to 2.00
Setting Range
Default
0.00 to 2.00
0
0.10
1.00
5
171