5.7 H: Terminal Functions
Example 3: Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.
Figure 5.33
YEA_TM
only
10 V
Output Voltage
3 V
0 V
0%
■
H4-07, H4-08: Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
No.
H4-07
H4-08
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
◆ H5: MEMOBUS/Modbus Serial Communication
Serial communication is possible in the drive using the built-in RS-422/485 port (terminals R+, R-, S+, S-) and
programmable logic controllers (PLCs) or similar devices running the MEMOBUS/Modbus protocol.
The H5- parameters are used to set up the drive for MEMOBUS/Modbus Communications. Refer to
Modbus Communications on page 443
222
H4-07, 08 = 0
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor Value
Figure 5.33 Analog Output Gain and Bias Setting Example 3
Parameter Name
Terminal FM Signal Level Selection
Terminal AM Signal Level Selection
for detailed descriptions of the H5- parameters.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
H4-07, 08 = 1
10V
Output Voltage
3 V
-100%
100%
Monitor Value
-4 V
-10 V
Setting Range
0 or 1
0 or 1
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
Default
0
0
MEMOBUS/