5.5
E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
◆ E1: V/f Pattern
■
E1-01: Input Voltage Setting
Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the
nominal voltage of the AC power supply.
NOTICE: Set parameter E1-01 to match the input voltage of the drive. The drive input voltage (not motor voltage) must be set in E1-01
for the protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.
No.
E1-01
<1>
<1> Values shown here are specific to 200 V class drives; double the values for 400 V class drives. Multiply value by 2.875 for 600 V class drives.
E1-01 Related Values
For 400 V class drives, the input voltage setting determines the undervoltage detection levels.
Setting Value of
Voltage
200 V Class
All settings
setting ≥ 400 V
400 V Class
setting < 400 V
600 V Class
All settings
<1> The braking transistor operation levels are valid for the internal braking transistor of the drive. When using an external CDBR braking chopper,
refer to the instruction manual of that unit.
■
E1-03: V/f Pattern Selection
No.
E1-03
Note: Parameter is not reset to the default value when the drive is initialized using A1-03.
V/f Pattern Settings E1-04 to E1-13
■
Figure 5.13
illustrates the V/f pattern setting.
NOTICE: The motor may require more acceleration torque with drive operation than with a commercial power supply. Set a proper V/f
pattern by checking the load torque characteristics of the elevator to be used with the motor.
No.
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
<5>
E1-12
<5>
E1-13
<1> Setting range depends on the control mode being used. CLV allows a setting range of 10.0 to 120.0 Hz, while CLV/PM allows a setting range
of 4.0 to 120.0 Hz.
<2> Default setting is determined by the control mode (A1-02).
<3> Values shown here are for 200 V class drives. Double values when using a 400 V class unit. Multiply value by 2.875 for 600 V class drives.
<4> Default setting is determined by the drive model (o2-04).
<5> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<6> Auto-Tuning will set E1-13 to the same value as E1-05.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Parameter Name
Input Voltage Setting
E1-01
ov Detection Level
410 V
820 V
820 V
1040 V
Parameter Name
V/f Pattern Selection
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency Voltage
Minimum Output Frequency
Minimum Output Frequency Voltage
Middle Output Frequency 2
Middle Output Frequency Voltage 2
Base Voltage
5.5 E: Motor Parameters
Setting Range
155 to 255 V
(Approximate Values)
Braking Transistor
Operation Level
<1>
394 V
788 V
788 V
990 V
Setting Range
F
Setting Range
10.0 to 200.0 Hz
<1>
0.0 to 255.0 V
<3>
0.0 to 200.0 Hz
0.0 to 200.0 Hz
0.0 to 255.0 V
<3>
0.0 to 200.0 Hz
0.0 to 255.0 V
<3>
0.0 to 120.0 Hz
0.0 to 255.0 V
<3>
0.0 to 255.0 V
<3>
Default
230 V
Uv Detection Level
(L2-05)
190 V
380 V
350 V
500 V
Default
F
5
Default
<2>
230.0 V
<3>
<2>
3.0 Hz
<2> <3> <4>
<2>
<2> <3> <4>
0.0 Hz
0.0 V
<3>
0.0 V
<3> <6>
187