D.3 Ul And Csa Standards - YASKAWA L1000A Technical Manual

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

D.3 UL and CSA Standards

◆ UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing
and evaluation, and determined that their stringent standards for product safety have been met. For a product to receive
UL certification, all components inside that product must also receive UL certification.
Figure D.7
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued
compliance when using this drive in combination with other equipment, meet the following conditions:
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
Ambient Temperature
IP00 enclosure with top protective cover: -10 to +40°C (14 to 104°F)
IP00 enclosure: -10 to +50°C (14 to 122°F)
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of UL
Listed closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-LU20085 through
20415, 40045 through 40605, and 50032 to 50200. Use only the tools recommended by the terminal
manufacturer for crimping.
The wire gauges listed in
Table D.4
gauge selections.
Table D.4 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Model
CIMR-LU
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
20008
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
20011
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
20014
B1, B2
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Figure D.7 UL/cUL Mark
and
Table D.5
are Yaskawa recommendations. Refer to local codes for proper wire
Recommended Gauge
Terminal
AWG, kcmil
14
14
10
12
14
10
10
10
10
Applicable Gauge
AWG, kcmil
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
<1>
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
<1>
12 to 10
14 to 10
14 to 10
14 to 10
14 to 10
<1>
D.3 UL and CSA Standards
Screw
Tightening Torque
Size
Nm (lb.in.)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
D
481