5.3 C: Tuning

◆ C6: Carrier Frequency

C6-03: Carrier Frequency
Sets the carrier frequency.
No.
C6-03
C6-06: PWM Method
Determines how the drive should perform pulse width modulation.
No.
C6-06
Setting 0: 2-phase/3-phase conversion
Setting 1: 2-phase modulation
Setting 2: 3-phase modulation
Note: The drive rated output current is reduced with setting 2. Contact Yaskawa or a Yaskawa representative for details.
C6-09: Carrier Frequency during Rotational Auto-Tuning
Determines the carrier frequency while performing Rotational Auto-Tuning. Although this parameter rarely needs to be
changed, when overcurrent problems occur when Auto-Tuning a low impedance motor, it may be helpful to set C6-03 to
a high value before setting C6-09 to 1.
No.
C6-09
Setting 0: 5 kHz
Setting 1: Same value set to C6-03
C6-21: Inspection Operation Carrier Frequency
Sets the carrier frequency during Inspection Run.
No.
C6-21
Setting 0: Use the value set to C6-03
Setting 1: 2 kHz
C6-23: Carrier Frequency during Initial Motor Pole Search
Sets the carrier frequency when estimating the initial polarity.
No.
C6-23
Setting 0: 2 kHz
Setting 1: Use the value set to C6-03
C6-31: Carrier Frequency during Rescue Operation
Note: Available in drive software PRG: 7016 or later.
Sets the carrier frequency during Rescue Operation.
No.
C6-31
Setting 0: Use the value set to C6-03
Setting 1: 2 kHz
182
Parameter Name
Carrier Frequency
Parameter Name
PWM Method
Parameter Name
Carrier Frequency during Rotational Auto-Tuning
Parameter Name
Inspection Operation Carrier Frequency
Parameter Name
Carrier Frequency during Initial Motor Pole Search
Parameter Name
Carrier Frequency during Rescue Operation
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Setting Range
1.0 to 15.0 kHz
Setting Range
0 to 2
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0 or 1
Setting Range
0, 1
Default
Determined by o2-04
Default
0
Default
0
Default
1
Default
0
Default
0