Changing Parameter Settings Or Values - YASKAWA L1000A Technical Manual

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

4.3 The Drive and Programming Modes

◆ Changing Parameter Settings or Values

This example explains changing C1-02 (Deceleration Ramp 1) from 1.50 seconds (default) to 2.50 seconds.
1.
Turn on the power to the drive. The initial display appears.
2.
Press
or
until the Parameter Setting Mode screen appears.
3.
Press
to enter the parameter menu tree.
4.
Press
or
to select the C parameter group.
5.
Press
two times.
6.
Press
or
to select the parameter C1-02.
7.
Press
to view the current setting value (1.5 s). The left most digit flashes.
8.
Press
,
or
F1
F2
left
right
9.
Press
and enter 0020.0.
10.
Press
to confirm the change.
11.
The display automatically returns to the screen shown in Step 4.
100
Step
until the desired number is selected. "1" flashes.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Display/Result
- MODE -
DRV
Rdy
Speed Ref (OPR)
U1-01= 0.00%
U1-02= 0.00%
RSEQ
U1-03= 0.00A
LREF
FWD
FWD/REV
- MODE -
PRG
Programming
HELP
FWD
DATA
-PRMSET-
PRG
Initialization
A1-00=
0
Select Language
FWD
-PRMSET-
PRG
Basic Setup
C1-01 =
1.50 sec
Accel Ramp 1
FWD
-PRMSET-
-PRMSET-
PRG
Accel/Decel
Accel Ramp 1
C1-01=
C1-01=
1.50 sec
(0.0~600.00)
Accel Ramp 1
"1.50 sec"
FWD
FWD
-PRMSET-
PRG
Decel Ramp 1
C1-02=
1.50 sec
(0.0~600.00)
"1.50 sec"
FWD
-PRMSET-
PRG
Decel Ramp 1
C1-02= 001.50 sec
(0.0~600.00)
"1.50 sec"
FWD
-PRMSET-
PRG
Decel Ramp 1
C1-02=001.50 sec
(0.0~600.00)
"1.50 sec"
FWD
-PRMSET-
PRG
Decel Ramp 1
C1-02=002.50 sec
(0.0~600.00)
"1.50 sec"
FWD
Entry Accepted
-PRMSET-
PRG
C1-02=
2.50 sec
(0.0~600.00)
"1.50 sec"
FWD
PRG
1.50 sec