F5: Digital Output Card Settings - YASKAWA L1000A Technical Manual

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

5.6 F: Option Settings
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Terminal V1
1.
View the value set to F4-02 (Terminal V1 Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in F4-01 is output at terminal V1.
2.
Adjust F4-02 while viewing the monitor connected to the terminal V1.
3.
View the value set to F4-05 on the digital operator. Terminal V1 outputs a voltage equal to 0% of the monitor
selected by the setting value of F4-01.
4.
Adjust F4-05 while viewing the output signal on the terminal V1.
Terminal V2
1.
View the value set to F4-02 (Terminal V2 Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being viewed in F4-03 is output at terminal V2.
2.
Adjust F4-04 while viewing the monitor connected to the terminal V2.
3.
View the value set to F4-06 on the digital operator. Terminal V2 will output a voltage equal to 0% of the monitor
selected by the setting value of F4-03.
4.
Adjust F4-06 while viewing the output signal on the terminal V2.
F4-07, F4-08: Terminal V1, V2 Signal Level Selection
Sets the output signal level for terminals V1 and V2.
No.
F4-07
F4-08
Setting 0: 0 to 10 V
Setting 1: -10 to 10 V

◆ F5: Digital Output Card Settings

These parameters set up the drive for operation with the digital output option card DO-A3. Refer to the instruction manual
packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.
F5-01 through F5-08: Digital Output Option Card Terminal Function Selection
When F5-09 = 2, the parameters listed in the table below are used to assign functions to the output terminals on the option
card.
No.
F5-01
F5-02
F5-03
F5-04
F5-05
F5-06
F5-07
F5-08
F5-09: DO-A3 Output Mode Selection
Determines how the DO-A3 option card works with the drive.
No.
F5-09
Setting 0: Separate output functions for each of 8 terminals
Setting 1: Binary output
Setting 2: Output functions assigned by F5-01 through F5-08
200
Parameter Name
Terminal V1 Signal Level Selection
Terminal V2 Signal Level Selection
Parameter Name
Terminal P1-C1 Output Selection
Terminal P2-C2 Output Selection
Terminal P3-C3 Output Selection
Terminal P4-C4 Output Selection
Terminal P5-C5 Output Selection
Terminal P6-C6 Output Selection
Terminal M1-M2 Output Selection
Terminal M3-M4 Output Selection
Parameter Name
DO-A3 Output Mode Selection
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Setting Range
Default
0, 1
0, 1
Setting Range
0 to 161
0: During run
0 to 161
1: Zero speed
0 to 161
2: Speed agree 1
0 to 161
4: Speed detection 1
0 to 161
6: Drive ready (READY)
0 to 161
37: During frequency output
0 to 161
F: Not used
0 to 161
F: Not used
Setting Range
0 to 2
1
1
Default
Default
0