N9: Current Detection Adjustments - YASKAWA L1000A Technical Manual

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

5.9 n: Special Adjustments
Setting 0: Disabled
After searching for the rotor pole position one time, the drive starts using the detected rotor position. If the detected
position is wrong, an error occurs when the drive attempts to run the motor. The initial pole search takes approximately
1.5 s.
Setting 1: Enabled
The rotor pole position search is executed multiple times. The drive starts using the detected rotor position only if there is
no difference between the search results. Otherwise a dv8 error will be output. The initial pole search takes approximately
1.5 to 5.0 s.
Other Settings
Parameters n8-29 to n8-33 can be used to adjust the current control loop. Adjustment is not normally required.
Parameter n8-62 sets a voltage limit in order to prevent voltage saturation.
n8-29: q-Axis Current Control Gain during Normal Operation
Sets the q-Axis proportional gain for the automatic current regulator.
No.
n8-29
n8-30: q-Axis Current Control Integral Time during Normal Operation
Sets the q-Axis integral time for the automatic current regulator.
No.
n8-30
n8-32: d-Axis Current Control Gain during Normal Operation
Sets the d-Axis proportional gain for the automatic current regulator.
No.
n8-32
n8-33: d-Axis Current Control Integral Time during Normal Operation
Sets the d-Axis integral time for the automatic current regulator.
No.
n8-33
n8-62: Output Voltage Limit
Sets the output voltage limit to prevent voltage saturation of the motor. Avoid setting this value higher than the input
voltage on the motor nameplate to maintain optimum motor performance.
No.
n8-62
<1>
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.

◆ n9: Current Detection Adjustments

n9-60: A/D Conversion Start Delay
Sets a delay time used for A/D conversion of the current. This value rarely needs to be changed. However, it can help to
resolve speed ripple problems at constant speed when using a PM motor. Prior to adjusting this value, make sure all other
parameters (motor data, speed loop settings) are adjusted correctly.
No.
n9-60
248
Parameter Name
q-Axis Current Control Gain during Normal Operation
Parameter Name
q-Axis Current Control Integral Time during Normal Operation
Parameter Name
d-Axis Current Control Gain during Normal Operation
Parameter Name
d-Axis Current Control Integral Time during Normal Operation
Parameter Name
Output Voltage Limit
Parameter Name
A/D Conversion Start Delay
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Setting Range
0 to 2000 rad/s
Setting Range
0.0 to 100.0 ms
Setting Range
0 to 2000 rad/s
Setting Range
0.0 to 100.0 ms
Setting Range
0.0 to 230.0 Vac
Setting Range
0.0 to 40.0 μs
Determined by o2-04
Default
1000 rad/s
Default
10.0 ms
Default
1000 rad/s
Default
10.0 ms
Default
200 Vac
Default