◆ Installation Orientation and Spacing

WARNING! Fire Hazard. Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet. Failure to comply
could result in overheating and fire. When drives are placed inside the same enclosure panel, install proper cooling to ensure air
entering the enclosure does not exceed 40
Installation Orientation
Install the drive upright as illustrated in
page 42
for details on installing the drive.
Figure 2.1
Installation Spacing
Figure 2.2
shows the installation distance required to maintain sufficient space for airflow and wiring.
Figure 2.2
Side Clearance
A
B
A
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
°
°
C (104
F).
Figure 2.1
to maintain proper cooling. Refer to
OK
Figure 2.1 Correct Installation Orientation
Top/Bottom Clearance
C
B
C
A – 50 mm (1.97 in.) minimum
B – 30 mm (1.18 in.) minimum
Figure 2.2 Correct Installation Spacing
Not OK
Not OK
D
C – 120 mm (4.72 in.) minimum
D – Airflow direction